Install Motormaster V Controls

The Motormaster V control is a motor speed control device
which adjusts condenser fan motor speed in response to
declining liquid refrigerant pressure. A properly applied
Motormaster V control extends the operating range of air-
conditioning systems and permits operation at lower outdoor
ambient temperatures.

The minimum ambient temperatures at which the unit will
operate are:

To operate down to the ambient temperatures listed,
Motormaster V controls (Fig. 23) must be added. Field-
fabricated and installed wind baffles are also required for all
units (see Fig. 21). The Motormaster V control permits opera-
tion of the unit to an ambient temperature of –20 F. The control
regulates the speed of 3-phase fan motors that are compatible
with the control. These motors are factory installed.

See Table 6 for the Motormaster V control accessory package
usage. Table 7 shows applicable voltages and motors.
Replacement of a motor IS NOT REQUIRED ON CUR-
RENT PRODUCTION UNITS
since the control is compati-
ble with the factory-installed fan motors. Only field wiring
control is required.

Install the Motormaster V control per instructions supplied
with accessory.

Table 6 — Motormaster V Control Package Usage

Table 7 — Applicable Voltages and Motors

XIII. STEP 13 — ADJUST FACTORY-INSTALLED OPTIONS

A. Optional EconoMi$erIV

See Fig. 24 and 25 for EconoMi$erIV component locations.

NOTE: These instructions are for installing the optional
EconoMi$erIV only. Refer to the accessory EconoMi$erIV
installation instructions when field installing an EconoMi$erIV
accessory.

To complete installation of the optional EconoMi$erIV, per-
form the following procedure.

1. Remove the EconoMi$erIV hood. Refer to Step 11 —

Install Outdoor-Air Hood on page 11 for information
on removing and installing the outdoor-air hood.

2. Relocate outdoor air temperature sensor from ship-

ping position to operation position on EconoMi$erIV.
See Fig. 24.

IMPORTANT: Failure to relocate the sensor will result in the
EconoMi$erIV not operating properly.

3. Re-install economizer hood.

4. Install all EconoMi$erIV accessories. EconoMi$erIV

wiring is shown in Fig. 26.

Outdoor air leakage is shown in Table 8. Return air pressure
drop is shown in Table 9.

TEMPERATURE OPERATING LIMITS — F°

Standard Unit

Unit with Low Ambient Kit

Unit with MMV Control

40

25

–20

UNIT

VOLTAGE

ITEM DESCRIPTION

579F180-300

208/230

CRLOWAMB015A00

460

CRLOWAMB016A00

VOLTAGE

COMPATIBLE MOTOR

208/230-3-60

HD52AK654

460-3-60

HD52AK654

SENSOR
LOCATION

HAIRPIN END

SENSOR
LOCATION

HAIRPIN END

NOTE: Dimensions in ( ) are in mm.

Fig. 21 — Wind Baffle Details

579F180

579F216

NOTE: All sensors are located on the eighth hairpin up from the
bottom.

Fig. 22 — Motormaster® I Sensor Locations