Table 14 — Fan Performance — 579F216 and 240 (Low Heat Units)

LEGEND

NOTES:

1. Standard low-medium static drive range for size 216 is 910 to 1095 rpm.

Standard low-medium static drive range for size 240 is 1002 to 1225 rpm.
Alternate high-static drive range for size 216 is 1069 to 1287. Alternate high-
static drive range for size 240 is 1193 to 1458 rpm. Other rpms require a
field-supplied drive.

2. Maximum continuous bhp for size 216 is 5.90. Maximum continuous bhp for

size 240 is 8.7 (208/230 v) or 9.5 (460 v). The maximum continuous watts for
size 216 is 5180. The maximum continuous watts for size 240 is 7915

(208/230 v) or 8640 (460 v). Do not adjust motor rpm such that motor maxi-
mum bhp and/or watts is exceeded at the maximum operating cfm.

3. Static pressure losses (i.e.,EconoMi$erIV) must be added to external static

pressure before entering Fan Performance table.

4. Interpolation is permissible. Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and casing losses. See

Table 21 for accessory/FIOP static pressure information.

6. Extensive motor and drive testing on these units ensures that the full horse-

power and watts range of the motor can be utilized with confidence. Using
the fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.

7. Use of a field-supplied motor may affect wiring size. Contact your local

Bryant representative for details.

Table 15 — Fan Performance — 579F300 (Low Heat Units)

LEGEND

NOTES:

1. Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-

static drive range is 1332 to 1550. Other rpms require a field-supplied drive.

2. Maximum continuous bhp is 10.2 (208/230 v) or 11.8 (460 v) and the maxi-

mum continuous watts are 9510 (208/230 v) or 11,000 (460 v). Do not adjust
motor rpm such that motor maximum bhp and/or watts is exceeded at the
maximum operating cfm.

3. Static pressure losses (i.e., EconoMi$erIV) must be added to external static

pressure before entering Fan Performance table.

4. Interpolation is permissible. Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and casing losses. See

Table 21 for accessory/FIOP static pressure information.

6. Extensive motor and drive testing on these units ensures that the full horse-

power and watts range of the motor can be utilized with confidence. Using
the fan motors up to the watts or bhp rating shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be affected.

7. Use of a field-supplied motor may affect wiring size. Contact your local

Bryant representative for details.

AIRFLOW

(cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5,500

755

2.27

1908

831

2.58

2171

901

2.91

2443

968

3.24

2723

1031

3.58

3009

1091

3.93

3302

6,000

810

2.72

2287

881

3.04

2556

947

3.37

2833

1010

3.71

3116

1070

4.05

3406

1127

4.40

3702

6,500

866

3.22

2710

932

3.55

2985

994

3.88

3266

1054

4.23

3554

1111

4.57

3847

1166

4.93

4146

7,000

923

3.78

3177

985

4.11

3458

1044

4.45

3744

1100

4.80

4036

1155

5.15

4333

1207

5.51

4635

7,500

980

4.39

3690

1038

4.73

3976

1094

5.07

4267

1148

5.43

4564

1200

5.78

4864

1250

6.15

5170

8,000

1038

5.06

4251

1093

5.40

4542

1146

5.75

4838

1197

6.11

5138

1246

6.47

5443

1294

6.84

5752

8,500

1096

5.78

4859

1148

6.13

5156

1198

6.49

5456

1247

6.85

5761

1294

7.22

6070

1340

7.59

6382

9,000

1154

6.56

5517

1204

6.92

5818

1251

7.28

6123

1298

7.65

6432

1343

8.02

6745

1388

8.40

7062

9,500

1213

7.40

6224

1260

7.77

6531

1306

8.13

6840

1350

8.51

7154

1394

8.88

7471

1436

9.26

7791

10,000

1272

8.30

6983

1317

8.67

7294

1360

9.05

7608

1403

9.43

7926

1445

9.81

8247

1486

10.19

8570

AIRFLOW

(cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.4

1.6

1.8

1.9

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

5,500

1149

4.28

3602

1204

4.65

3907

1258

5.02

4217

1284

5.20

4375

1309

5.39

4533

6,000

1183

4.76

4003

1236

5.13

4310

1288

5.50

4622

1313

5.68

4780

1337

5.87

4939

6,500

1219

5.29

4450

1270

5.66

1459

1320

6.03

5073

1344

6.22

5232

1368

6.41

5391

7,000

1258

5.88

4942

1307

6.25

5253

1355

6.62

5569

1378

6.81

5729

1402

7.00

5890

7,500

1299

6.52

5480

1346

6.89

5794

1392

7.27

6113

1415

7.46

6273

1437

7.65

6435

8,000

1341

7.21

6065

1387

7.59

6383

1392

7.97

6704

1453

8.16

6866

1475

8.36

7028

8,500

1385

7.97

6699

1429

8.35

7019

1472

8.73

7343

1493

8.93

7506

1514

9.12

7670

9,000

1431

8.78

7382

1473

9.15

7705

1515

9.55

8032

1535

9.75

8196

9,500

1478

9.65

8114

1519

10.04

8441

10,000

Bhp

Brake Horsepower

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

AIRFLOW

(cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

941

3.35

2769

1002

3.80

3140

1061

4.27

3528

1117

4.76

3934

1171

5.27

4356

1224

5.80

4794

7,500

999

4.05

3348

1057

4.53

3742

1112

5.02

4152

1166

5.54

4579

1218

6.07

5020

1268

6.63

5478

8,000

1058

4.85

4007

1113

5.35

4424

1165

5.87

4856

1216

6.41

5304

1266

6.97

5766

1314

7.55

6243

8,500

1117

5.74

4750

1169

6.28

5190

1219

6.83

5645

1268

7.40

6114

1315

7.98

6597

1361

8.58

7094

9,000

1177

6.75

5583

1226

7.31

6047

1274

7.89

6524

1320

8.48

7015

1365

9.09

7520

1410

9.72

8037

9,500

1237

7.98

6511

1284

8.46

6999

1329

9.07

7499

1374

9.69

8012

1417

10.33

8538

1459

10.98

9076

10,000

1297

9.12

7450

1342

9.74

8051

1385

10.37

8574

1428

11.02

9110

1469

11.68

9657

1510

12.36

10217

10,500

1358

10.49

8674

1400

11.14

9209

1442

11.80

9755

1483

12.47

10314

1523

13.16

10883

11,000

1418

12.00

9919

1459

12.67

10478

11,250

1449

12.80

10585

AIRFLOW

(cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

1274

6.35

5248

1323

6.92

5718

1371

5.54

6204

7,500

1316

7.20

6960

1364

7.79

6437

1410

6.41

6939

8,000

1360

8.14

6734

1406

8.76

7239

1450

7.40

7759

8,500

1406

9.20

7605

1449

9.83

8129

1492

8.48

8666

9,000

1453

10.36

8568

1495

11.02

9111

1536

9.69

9667

9,500

1501

11.64

9627

1541

12.32

10190

10,000

10,500

11,000

11,250

Bhp

Brake Horsepower

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

Advertising