Bryant DURAPAC 579F User Manual

Page 37

Advertising
background image

—

37

—

LEGEND AND NOTES FOR FIG. 46 AND 47

QT

— Quadruple Terminal

RAT

— Return Air Temperature Sensor

RS

— Rollout Switch

SN

— Sensor

SW

— Switch

TB

— Terminal Block

TC

— Thermostat Cooling

TH

— Thermostat Heating

TRAN — Transformer

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Splice

Factory Wiring

Field Wiring

Option/Accessory Wiring
To indicate common potential only;
not to represent wiring.

Economizer Motor

Remote POT Field Accessory

OAT Sensor

Disch Air Sensor

RAT Accessory Sensor

Low Ambient Lockout Switch

AHA

— Adjustable, Heat Anticipator

BRK W/AT — Breaks With Amp Turns
C

— Contactor, Compressor

CAP

— Capacitor

CB

— Circuit Breaker

CC

— Cooling Compensator

CLO

— Compressor Lockout

COMP

— Compressor Motor

CTD

— Compressor Time Delay

DM

— Damper Motor

DU

— Dummy Terminal

EQUIP

— Equipment

FU

— Fuse

GND

— Ground

HPS

— High-Pressure Switch

IAQ

— Indoor Air Quality Sensor

IDM

— Induced Draft Motor

IFC

— Indoor-Fan Contactor

IFM

— Indoor-Fan Motor

IFR

— Indoor Fan Relay

IGC

— Integrated Gas Unit Controller

L

— Light

LALS

— Low Ambient Temperature

Compressor Lockout Switch

LPS

— Low-Pressure Switch

LS

— Limit Switch

MGV

— Main Gas Valve

NEC

— National Electrical Code

OAT

— Outdoor Air Temperature Sensor

OCCUP

— Occupancy Sensor

OFC

— Outdoor Fan Contactor

OFM

— Outdoor Fan Motor

PL

— Plug Assembly

PMR

— Phase Monitor Relay

LEGEND

NOTES:

1. Compressor and/or fan motors thermally protected; three phase motors protected against primary single-

phasing conditions.

2. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equiv-

alent.

3. TRAN1 is wired for 230-v operation. If unit is 208-v, disconnect the BLK wires from the ORN TRAN wire

and reconnect to the RED TRAN wire. Apply wirenuts to wires.

4. CB1, 2 Must Trip Amps are equal to or less than 156% FLA, IFCB 140%.
5. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices.

Before replacing CLO, check these devices.

6. Jumpers are omitted when unit is equipped with economizer.
7. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole,

double-throw contact. An underlined number signifies a normally closed contact. A plain (no line) number
signifies a normally open contact.

8. Remove jumper between RC & RH.
9. 620 Ohm, 1 watt, 5% resistor should be removed only when using differential enthalpy or dry bulb.

10. If a separate field-supplied 24-v transformer is used for the IAQ sensor power supply, it cannot have the

secondary of the transformer grounded.

11. OAT sensor is shipped inside unit and must be relocated in the field for proper operation.
12. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set

control minimum position POT to the minimum position.

Advertising