Bryant DURAPAC 579F User Manual

Page 39

Advertising
background image

39

G. EconoMi$erIV Troubleshooting Completion

This procedure is used to return the EconoMi$erIV to opera-
tion. No troubleshooting or testing is done by performing the
following procedure.

1. Disconnect power at TR and TR1.

2. Set enthalpy potentiometer to previous setting.

3. Set DCV maximum position potentiometer to previ-

ous setting.

4. Set minimum position, DCV set point, and exhaust

potentiometers to previous settings.

5. Remove 620-ohm resistor from terminals S

R

and +.

6. Remove 1.2 kilo-ohm checkout resistor from terminals

S

O

and +. If used, reconnect sensor from terminals S

O

and +.

7. Remove jumper from TR to N.

8. Remove jumper from TR to 1.

9. Remove 5.6 kilo-ohm resistor from T and T1. Recon-

nect wires at T and T1.

10. Remove jumper from P to P1. Reconnect device at P

and P1.

11. Apply power (24 vac) to terminals TR and TR1.

Table 26 — Cooling Service Analysis

LEGEND

TXV — Thermostatic Expansion Valve

PROBLEM

CAUSE

REMEDY

Compressor and Condenser
Fan
Will Not Start.

Power failure.

Call power company.

Fuse blown or circuit breaker tripped.

Replace fuse or reset circuit breaker.

Defective thermostat, contactor, transformer, or control
relay.

Replace component.

Insufficient line voltage.

Determine cause and correct.

Incorrect or faulty wiring.

Check wiring diagram and rewire correctly.

Thermostat setting too high.

Lower thermostat setting below room temperature.

Three phase power incorrectly connected (579F180 and 216
only). Indicated by flashing red LED on Phase Monitor Relay
(PMR) board (see Control Box Component Arrangement for
location).

Correct field power phasing.

Compressor Will Not Start
but Condenser Fan Runs.

Faulty wiring or loose connections in compressor circuit.

Check wiring and repair or replace.

Compressor motor burned out, seized, or internal overload
open.

Determine cause. Replace compressor.

Defective overload.

Determine cause and replace.

Compressor locked out

Determine cause for safety trip and reset lockout.

One leg of 3-phase power dead.

Replace fuse or reset circuit breaker.
Determine cause.

Compressor Cycles
(other than normally
satisfying thermostat).

Refrigerant overcharge or undercharge.

Recover refrigerant, evacuate system, and recharge
to nameplate.

Defective compressor.

Replace and determine cause.

Insufficient line voltage.

Determine cause and correct.

Blocked condenser.

Determine cause and correct.

Defective overload.

Determine cause and replace.

Defective thermostat.

Replace thermostat.

Faulty condenser-fan motor.

Replace.

Restriction in refrigerant system.

Locate restriction and remove.

Compressor Operates
continuously.

Dirty air filter.

Replace filter.

Unit undersized for load.

Decrease load or increase unit size.

Thermostat set too low.

Reset thermostat.

Low refrigerant charge.

Locate leak, repair, and recharge.

Air in system.

Recover refrigerant, evacuate system, and recharge.

Condenser coil dirty or restricted.

Clean coil or remove restriction.

Excessive Head Pressure.

Dirty air filter.

Replace filter.

Dirty condenser coil.

Clean coil.

Refrigerant overcharged.

Recover excess refrigerant.

Faulty TXV.

1. Check TXV bulb mounting and secure tightly to suction line.
2. Replace TXV if stuck open or closed.

Air in system.

Recover refrigerant, evacuate system, and recharge.

Condenser air restricted or air short-cycling.

Determine cause and correct.

Head Pressure Too Low.

Low refrigerant charge.

Check for leaks, repair, and recharge.

Restriction in liquid tube.

Remove restriction.

Excessive Suction
Pressure.

High heat load.

Check for source and eliminate.

Faulty TXV.

1. Check TXV bulb mounting and secure tightly to suction line.
2. Replace TXV if stuck open or closed.

Refrigerant overcharged.

Recover excess refrigerant.

Suction Pressure Too Low.

Dirty air filter.

Replace filter.

Low refrigerant charge.

Check for leaks, repair, and recharge.

Metering device or low side restricted.

Remove source of restriction.

Faulty TXV.

1. Check TXV bulb mounting and secure tightly to suction line.
2. Replace TXV if stuck open or closed.

Insufficient evaporator airflow.

Increase air quantity. Check filter and replace if necessary.

Temperature too low in conditioned area.

Reset thermostat.

Field-installed filter drier restricted.

Replace.

Advertising