Bryant DURAPAC 579F User Manual

Page 17

Advertising
background image

17

Table 11 — EconoMi$erIV Sensor Usage

*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many different base units. As such, these kits may contain parts that will not be needed

for installation.

†CGCDXSEN004A00 is an accessory CO

2

sensor.

**CGCDXASP001A00 is an accessory aspirator box required for duct-mounted applications.

Differential Enthalpy Control

For differential enthalpy control, the EconoMi$erIV controller
uses two enthalpy sensors (HH57AC078 and
CRENTDIF004A00), one in the outside air and one in the
return airstream on the EconoMi$erIV frame. The
EconoMi$erIV controller compares the outdoor air enthalpy to
the return air enthalpy to determine EconoMi$erIV use. The
controller selects the lower enthalpy air (return or outdoor) for
cooling. For example, when the outdoor air has a lower
enthalpy than the return air and is below the set point, the
EconoMi$erIV opens to bring in outdoor air for free cooling.

Replace the standard outside air dry bulb temperature sen-
sor with the accessory enthalpy sensor in the same mounting
location. See Fig. 24. Mount the return air enthalpy sensor
in the return airstream. See Fig. 29. The outdoor enthalpy
changeover set point is set with the outdoor enthalpy set
point potentiometer on the EconoMi$erIV controller. When
using this mode of changeover control, turn the enthalpy set
point potentiometer fully clockwise to the D setting.

NOTE: Remove 620-ohm resistor if differential enthalpy sen-
sor is installed.

APPLICATION

ECONOMI$ERIV WITH OUTDOOR AIR

DRY BULB SENSOR

ECONOMI$ERIV WITH SINGLE

ENTHALPY SENSOR

Accessories Required

Accessories Required

Outdoor Air Dry Bulb

None. The outdoor air dry bulb sensor is factory installed.

CRTEMPSN002A00*

Differential Dry Bulb

CRTEMPSN002A00*

(2) CRTEMPSN002A00*

Single Enthalpy

HH57AC078

None. The single enthalpy sensor is factory installed.

Differential Enthalpy

HH57AC078

and

CRENTDIF004A00*

CRENTDIF004A00*

CO

2

for DCV Control using a

Wall-Mounted CO

2

Sensor

CGCDXSEN004A00

CO

2

for DCV Control using a

Duct-Mounted CO

2

Sensor

CGCDXSEN004A00†

and

CGCDXASP001A00**

Fig. 27 — EconoMi$erIV Controller Potentiometer

and LED Locations

LED ON

LED ON

LED ON

LED ON

LED OFF

19

18

LED OFF

LED OFF

LED OFF

17

16

15

14

13

12

11

10

9

40

45

50

55

60

65

70

75

80

85

90

95

100

DEGREES FAHRENHEIT

mA

D

C

B

A

Fig. 28 — Outside Air Temperature

Changeover Set Points

IAQ

SENSOR

RETURN AIR

TEMPERATURE

OR ENTHALPY

SENSOR

TR

1

24

Va

c

COM

TR

24

Va

c

HO

T

1

2

3

4

5

EF

EF

1

+

_

P1

T1

P

T

N

EXH

2V

10

V

EX

H

Set

Se

t

2V

10

V

2V

10

V

DC

V

DC

V

Fr

ee

Co

ol

B

C

A

D

SO

+

SR

+

SR

SO

AQ1

AQ

DC

V

Mi

n

Pos

Op

en

Ma

x

N1

Fig. 29 — Return Air Temperature or Enthalpy

Sensor Mounting Location