III.

ACCESSORIES

1. Electronic Air Cleaner (EAC)

Two spring clamp terminals (for 12 gage maximum, solid
or stranded wire), marked EAC-1 and EAC-2, are provided
for EAC connection. (See Fig. 25.) These terminals are
energized with 115v (1.5-amp maximum) during blower
motor operation. To connect EAC power leads to furnace
control center, strip approximately 1/8 in. of insulation from
wire. Open terminal by depressing switch arm with a
screwdriver or finger, and insert wire as shown in Fig. 26.

2. Humidifier (HUM)

Screw terminals (HUM and C

OM

) are provided for 24-v

humidifier connection. (See Fig. 24.) HUM terminal is
energized with 24v (0.5-amp maximum) after inducer
motor prepurge period.

NOTE:

A field-supplied, 115-v controlled relay connected to

EAC terminals may be added if humidifier operation is desired
during blower operation.

TABLE 4—ELECTRICAL DATA

UNIT

SIZE

VOLTS—
HERTZ—

PHASE

OPERATING

VOLTAGE RANGE

MAX

UNIT

AMPS

UNIT

AMPACITY†

MIN

WIRE

SIZE

MAX WIRE

LENGTH

(FT)‡

MAX FUSE

OR CKT BKR

AMPS**

Max*

Min*

024040

115—60—1

127

104

6.1

8.4

14

44

15

036040

115—60—1

127

104

7.3

10.0

14

37

15

024060

115—60—1

127

104

6.1

8.4

14

44

15

036060

115—60—1

127

104

7.1

9.8

14

38

15

048060

115—60—1

127

104

9.5

12.8

14

29

15

036080

115—60—1

127

104

7.6

10.4

14

36

15

048080

115—60—1

127

104

10.0

13.4

14

28

15

060080

115—60—1

127

104

14.1

18.4

12

31

20

048100

115—60—1

127

104

10.2

13.5

14

27

15

060100

115—60—1

127

104

14.8

19.3

12

30

20

060120

115—60—1

127

104

14.6

19.1

12

30

20

060140

115—60—1

127

104

14.3

18.8

12

30

20

* Permissible limits of voltage range at which unit will operate satisfactorily.
† Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load

amps.

‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
** Time-delay fuse is recommended.

Fig. 25—Control Center

A93052

G

R

Y

W

3-AMP FUSE

Com

24V

HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX)

LED OPERATION &
STATUS LIGHT

HARNESS CONNECTOR

24V TRANSFORMER SEC-2

SPARE 1

SPARE 2

EAC 1 (BLACK)

EAC-ELECTRONIC AIR CLEANER
TERMINALS (115-VAC 1.5 AMP MAX)

EAC 2 (WHITE)

115-VAC (L2) NEUTRAL
CONNECTION

24V THERMOSTAT
TERMINALS

BLOWER SPEED
SELECTION TERMINALS

INDUCER MOTOR
CONNECTOR

115-VAC (L1)

POWER

SUPPLY

HOT SURFACE

IGNITOR

CONNECTOR

HEAT

COOL

BLOWER OFF DELAY
ADJUSTMENT SWITCH

SEC-1

TEST/TWIN

HUM

—20—