Bryant 350MAV User Manual

Page 36

Advertising
background image

TABLE 8—MODEL 350MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT

Continued

FOR USE WITH 040 THROUGH 120 SIZE FURNACES ONLY

(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

725

43

3.7

43

3.8

42

3.2

42

3.3

42

3.4

750

43

3.4

43

3.5

43

3.7

43

3.8

42

3.2

775

44

3.7

44

3.8

43

3.4

43

3.5

43

3.7

4001

800

44

3.5

44

3.6

44

3.7

44

3.8

43

3.4

825

44

3.2

44

3.4

44

3.5

44

3.6

44

3.7

to

850

45

3.7

45

3.8

44

3.3

44

3.4

44

3.5

875

45

3.5

45

3.6

45

3.7

44

3.2

44

3.3

5000

900

45

3.3

45

3.4

45

3.5

45

3.6

45

3.8

925

45

3.1

45

3.2

45

3.3

45

3.4

45

3.6

950

45

3.0

45

3.1

45

3.2

45

3.3

45

3.4

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

700

43

3.6

43

3.7

42

3.2

42

3.3

42

3.4

725

43

3.4

43

3.5

43

3.6

43

3.7

43

3.8

750

44

3.6

44

3.7

43

3.4

43

3.5

43

3.6

775

44

3.4

44

3.5

44

3.6

44

3.7

43

3.4

5001

800

44

3.2

44

3.3

44

3.4

44

3.5

44

3.6

825

45

3.6

45

3.7

44

3.2

44

3.3

44

3.4

to

850

45

3.4

45

3.5

45

3.6

45

3.8

44

3.2

875

45

3.2

45

3.3

45

3.4

45

3.6

45

3.7

6000

900

45

3.0

45

3.1

45

3.3

45

3.4

45

3.5

925

45

2.9

45

3.0

45

3.1

45

3.2

45

3.3

950

45

2.7

45

2.8

45

2.9

45

3.0

45

3.1

975

45

2.6

45

2.7

45

2.8

45

2.9

45

2.9

1000

45

2.5

45

2.5

45

2.6

45

2.7

45

2.8

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

650

42

3.2

42

3.3

42

3.4

42

3.5

42

3.6

675

43

3.6

43

3.7

43

3.8

42

3.2

42

3.3

700

44

3.8

43

3.4

43

3.6

43

3.7

43

3.8

6001

725

44

3.6

44

3.7

44

3.8

43

3.4

43

3.5

750

44

3.3

44

3.4

44

3.6

44

3.7

44

3.8

to

775

45

3.8

44

3.2

44

3.3

44

3.4

44

3.5

800

45

3.5

45

3.7

45

3.8

44

3.2

44

3.3

7000

825

45

3.3

45

3.4

45

3.6

45

3.7

45

3.8

850

45

3.1

45

3.2

45

3.4

45

3.5

45

3.6

875

45

3.0

45

3.1

45

3.2

45

3.3

45

3.4

—36—

Advertising