5. Chamfer outside edge of pipe for better distribution of

primer and cement.

6. Clean and dry all surfaces to be joined.

7. Check dry fit of pipe and mark insertion depth on pipe.

NOTE:

It is recommended that all pipes be cut, prepared, and

preassembled before permanently cementing any joint.

8. After pipes have been cut and preassembled, apply gener-

ous layer of cement primer to pipe fitting socket and end of
pipe to insertion mark. Quickly apply approved cement to
end of pipe and fitting socket (over primer). Apply cement
in a light, uniform coat on inside of socket to prevent
buildup of excess cement. Apply second coat.

9. While cement is still wet, twist pipe into socket with 1/4

turn. Be sure pipe is fully inserted into fitting socket.

10. Wipe excess cement from joint. A continuous bead of

cement will be visible around perimeter of a properly made
joint.

11. Handle pipe joints carefully until cement sets.

12. Support combustion-air and vent piping a minimum of

every 5 ft (3 ft for SDR-21 or -26 PVC) using perforated
metal hanging strap.

13. Slope combustion-air and vent pipes toward furnace a

minimum of 1/4 in. per linear ft with no sags between
hangers.

14. Use appropriate methods to seal openings where vent and

combustion-air pipes pass through roof or side wall.

III.

CONCENTRIC VENT AND COMBUSTION-AIR

TERMINATION KIT INSTALLATION

NOTE:

If these instructions differ from those packaged with

termination kit, follow kit instructions.

Combustion-air and vent pipes must terminate outside structure. A
factory accessory termination kit must be installed in 1 of the
installations shown in Fig. 31, 32, 33, 34, or 35. Four termination
kits are available.

1. The 2-in. termination bracket kit is for 1-in., 1-1/2 in., and

2-in. diameter 2-pipe termination systems.

2. The 3-in. termination bracket kit is for 2-1/2 in., 3-in., and

4-in. diameter 2-pipe termination systems.

3. The 2-in. concentric vent/air termination kit is for 1-in.,

1-1/2 in., 2-in., and 2-1/2 in. diameter pipe systems when
single penetration of wall or roof is desired.

4. The 3-in. concentric vent/air termination kit is for 2-1/2 in.,

3-in., and 4-in. diameter pipe systems when single penetra-
tion of wall or roof is desired.

NOTE:

Shaded parts in Fig. 31, 32, 33, 34, and 35 are considered

to be termination. These components should NOT be counted
when determining pipe diameter. Roof termination is preferred
since it is less susceptible to damage, has reduced chances to take
in contaminants, and has less visible vent vapors. (See Fig. 31 or
32.) Sidewall termination may require sealing or shielding of
building surfaces with a corrosive resistance material due to
corrosive combustion products of vent system.

A.

Extended Exposed Sidewall Pipes

Sidewall combustion-air and vent pipe terminations may be
extended beyond area shown in Fig. 34 or 35 in outside ambient by
insulating pipes as indicated in Table 7.

1. Determine combustion-air and vent pipe diameters, as

stated above, using total pipe length and number of elbows.

2. Using winter design temperature (used in load calculations),

find appropriate temperature for your application and fur-
nace model.

3. Determine required insulation thickness for exposed pipe

lengths.

NOTE:

Pipe length (ft) specified for maximum pipe lengths

located in unconditioned spaces cannot exceed total allowable pipe
length as specified in Table 6.

B.

Two-Pipe Termination Kit

1. Determine location for termination.

Consideration of the following should be made when
determining an appropriate location for termination kit.
a. Comply with all clearance requirements as stated in

Table 5.

b. Termination kit should be positioned where vent vapors

will not damage plants/shrubs or air conditioning equip-
ment.

TABLE 7—MAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH AND WITHOUT INSULATION

IN WINTER DESIGN TEMPERATURE AMBIENT*

UNIT

SIZE

WINTER DESIGN

TEMPERATURE

(°F)

MAX PIPE

DIAMETER

(IN.)

WITHOUT

INSULATION

WITH 3/8-IN. OR

THICKER INSULATION†

040

20

1-1/2

51

70

0

1-1/2

28

70

-20

1-1/2

16

70

060

20

2

65

70

0

2

35

70

-20

2

20

70

080

20

2-1/2

70

70

0

2-1/2

47

70

-20

2-1/2

28

70

100

20

3

70

70

0

3

50

70

-20

3

28

70

120

20

4

70

70

0

4

48

70

-20

4

23

70

140

20

4

70

70

0

4

57

70

-20

4

30

70

* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as

specified in Table 6.

† Insulation thickness based on R value of 3.5 per in.

—27—