Bryant 350MAV User Manual

Page 39

Advertising
background image

TABLE 9—MODEL 350MAV ORIFICE SIZE AND MANIFOLD PRESSURE FOR CORRECT INPUT

Continued

FOR USE WITH 140 SIZE FURNACES ONLY

(TABULATED DATA BASED ON 23,000 BTUH PER BURNER, DERATED 2% FOR EACH 1000 FT ABOVE SEA LEVEL)

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

725

41

3.6

41

3.7

41

3.8

40

3.6

40

3.8

750

42

3.7

42

3.8

41

3.6

41

3.7

41

3.8

4001

775

42

3.5

42

3.6

42

3.7

42

3.8

41

3.6

800

42

3.3

42

3.4

42

3.5

42

3.6

42

3.7

to

825

43

3.7

42

3.2

42

3.3

42

3.4

42

3.5

850

43

3.5

43

3.6

43

3.8

42

3.2

42

3.3

5000

875

43

3.3

43

3.4

43

3.6

43

3.7

43

3.8

900

43

3.1

43

3.3

43

3.4

43

3.5

43

3.6

925

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

950

43

2.8

43

2.9

43

3.0

43

3.1

43

3.2

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

700

41

3.5

41

3.7

41

3.8

40

3.6

40

3.7

725

42

3.7

42

3.8

41

3.5

41

3.6

41

3.8

750

42

3.4

42

3.5

42

3.7

42

3.8

41

3.5

775

42

3.2

42

3.3

42

3.4

42

3.5

42

3.7

5001

800

43

3.7

43

3.8

42

3.2

42

3.3

42

3.4

825

43

3.5

43

3.6

43

3.7

43

3.8

42

3.2

to

850

43

3.3

43

3.4

43

3.5

43

3.6

43

3.7

875

43

3.1

43

3.2

43

3.3

43

3.4

43

3.5

6000

900

43

2.9

43

3.0

43

3.1

43

3.2

43

3.3

925

43

2.7

43

2.8

43

2.9

43

3.0

43

3.1

950

43

2.6

43

2.7

43

2.8

43

2.9

43

3.0

975

43

2.5

43

2.6

43

2.6

43

2.7

43

2.8

1000

43

2.3

43

2.4

43

2.5

43

2.6

43

2.7

ALTITUDE

RANGE

(FT)

AVG GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

0.66

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

Only

650

41

3.8

40

3.6

40

3.7

40

3.8

39

3.7

675

41

3.5

41

3.6

41

3.7

40

3.6

40

3.7

6001

700

42

3.6

42

3.7

41

3.5

41

3.6

41

3.7

725

42

3.4

42

3.5

42

3.6

42

3.7

42

3.8

to

750

43

3.8

42

3.3

42

3.4

42

3.5

42

3.6

775

43

3.6

43

3.7

43

3.8

42

3.3

42

3.4

7000

800

43

3.4

43

3.5

43

3.6

43

3.7

43

3.8

825

43

3.2

43

3.3

43

3.4

43

3.5

43

3.6

850

43

3.0

43

3.1

43

3.2

43

3.3

43

3.4

875

43

2.8

43

2.9

43

3.0

43

3.1

43

3.2

—39—

Advertising