Performance data – Bryant 601A User Manual

Page 11

Advertising
background image

—11—

PERFORMANCE DATA

COOLING EXTENDED PERFORMANCE TABLE

HEATING EXTENDED PERFORMANCE TABLE

-10–20

HEATING EXTENDED PERFORMANCE TABLE 30–60

*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 18.

601A018 (1.5 TONS)

Temp (F)

Air Ent

Outdoor Coil

(Edb)

Indoor Entering Air—CFM/BF

525/0.094

700/0.155

750/0.151

Indoor Entering Air—Ewb (F)

72

67

63*

62

72

67

63*

62

72

67

63*

62

85

TC

20.8

19.3

18.5

17.7

21.4

19.8

18.6

18.3

21.5

19.8

18.6

18.4

SHC

10.7

13.5

14.7

16.2

11.4

14.8

14.7

18.3

11.5

15.1

14.7

18.4

kW

1.78

1.75

1.83

1.71

1.88

1.85

1.83

1.80

1.92

1.89

1.83

1.83

95

TC

20.0

18.6

17.8

16.7

20.6

19.0

17.8

17.6

20.7

19.1

17.8

17.8

SHC

10.5

13.3

14.8

15.7

11.2

14.9

14.8

17.6

11.4

15.3

14.8

17.8

kW

1.86

1.84

1.93

1.78

1.97

1.95

1.93

1.88

2.01

1.98

1.93

1.91

105

TC

19.3

17.5

17.0

15.9

19.7

18.0

17.0

16.7

19.8

18.0

16.9

17.3

SHC

10.3

12.8

14.3

15.2

11.1

14.5

14.5

16.7

11.3

15.0

13.7

16.8

kW

1.96

1.93

1.91

1.86

2.07

2.04

2.02

1.96

2.11

2.07

2.02

2.01

115

TC

18.3

16.5

16.1

15.0

18.7

16.5

16.2

15.9

18.7

16.6

15.9

16.7

SHC

9.8

12.2

13.7

14.5

10.8

13.9

14.2

15.4

11.0

14.4

12.6

15.7

kW

2.07

2.03

2.01

1.94

2.17

2.14

2.11

2.04

2.21

2.15

2.11

2.10

601A018 (1.5 TONS)

Temp (F)

Indoor Air Cfm (std)

Air Temperature Entering Outdoor Coil (F db at 70% rh)

Ent Indoor Coil

-10

0

10

17

20

60

525

TC

2.05

2.01

4.02

3.75

5.99

5.49

7.36

6.71

8.05

7.25

kW

1.10

1.19

1.28

1.34

1.37

700

TC

2.77

2.71

5.19

4.85

7.62

6.99

9.32

8.50

10.15

9.16

kW

1.15

1.24

1.33

1.39

1.42

750

TC

2.96

2.89

5.53

5.16

8.10

7.43

9.89

9.02

10.74

9.71

kW

1.17

1.26

1.34

1.41

1.44

70

525

TC

1.52

1.51

3.46

3.23

5.40

4.95

6.75

6.16

7.42

6.68

kW

1.09

1.19

1.29

1.36

1.40

700

TC

2.04

2.02

4.48

4.18

6.90

6.34

8.61

7.85

9.45

8.51

kW

1.15

1.25

1.35

1.41

1.45

750

TC

2.21

2.19

4.77

4.47

7.34

6.74

9.14

8.34

10.05

9.03

kW

1.17

1.27

1.36

1.43

1.46

80

525

TC

0.87

0.87

2.81

2.64

4.75

4.37

6.12

5.58

6.77

6.10

kW

1.07

1.19

1.30

1.38

1.41

700

TC

1.22

1.22

3.67

3.44

6.12

5.62

7.84

7.14

8.66

7.80

kW

1.14

1.25

1.36

1.43

1.47

750

TC

1.34

1.34

3.93

3.68

6.52

5.98

8.33

7.59

9.20

8.29

kW

1.16

1.26

1.37

1.45

1.48

601A018 (1.5 TONS)

Temp (F)

Indoor Air Cfm (std)

Air Temperature Entering Outdoor Coil (F db at 70% rh)

Ent Indoor Coil

30

40

47

50

60

60

525

TC

10.34

9.06

12.93

12.93

15.02

15.02

15.72

15.72

18.40

18.40

kW

1.47

1.59

1.69

1.72

1.83

700

TC

12.93

11.34

16.11

16.11

18.00

18.00

18.80

18.80

21.39

21.39

kW

1.52

1.63

1.69

1.72

1.80

750

TC

13.73

12.04

16.91

16.91

18.90

18.90

19.60

19.60

22.38

22.18

kW

1.54

1.64

1.70

1.72

1.79

70

525

TC

9.65

8.45

12.23

12.23

14.32

14.32

15.22

15.22

18.30

18.30

kW

1.50

1.63

1.73

1.77

1.92

700

TC

12.23

10.74

15.42

15.42

17.71

17.71

18.80

18.80

21.39

21.39

kW

1.55

1.67

1.76

1.80

1.88

750

TC

12.93

11.34

16.31

16.31

18.70

18.70

19.60

19.60

22.28

22.28

kW

1.57

1.69

1.77

1.80

1.88

80

525

TC

8.96

7.86

11.54

11.54

13.53

13.53

14.42

14.42

17.51

17.51

kW

1.53

1.66

1.77

1.81

1.98

700

TC

11.44

9.95

14.62

14.62

17.01

17.01

18.00

18.00

21.29

21.29

kW

1.58

1.71

1.81

1.85

1.97

750

TC

12.14

10.64

15.42

15.42

17.90

17.90

19.00

19.00

22.28

22.28

kW

1.59

1.72

1.83

1.86

1.98

Advertising