PERFORMANCE DATA (cont)

COOLING EXTENDED PERFORMANCE TABLE

HEATING EXTENDED PERFORMANCE TABLE

-10–20

HEATING EXTENDED PERFORMANCE TABLE 30–60

*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 18.

601A060 (5 TONS)

Temp (F)

Air Ent

Outdoor Coil

(Edb)

Indoor Entering Air—CFM/BF

1750/0.079

2000/0.099

2250/0.167

Indoor Entering Air—Ewb (F)

72

67

63*

62

72

67

63*

62

72

67

63*

62

85

TC

64.8

59.9

55.9

54.9

64.8

59.9

55.9

53.7

64.8

59.9

55.9

55.0

SHC

34.6

45.4

44.2

53.7

34.6

45.4

44.2

52.0

34.6

45.4

44.2

55.0

kW

5.73

5.64

5.59

5.59

5.73

5.64

5.59

5.61

5.73

5.64

5.59

5.58

95

TC

62.6

57.5

53.2

52.6

62.6

57.5

52.9

52.7

62.6

57.5

53.4

52.8

SHC

33.9

44.7

42.9

51.3

33.9

44.7

42.4

52.0

33.9

44.7

43.5

52.8

kW

6.21

6.11

6.09

6.10

6.21

6.11

6.08

6.05

6.21

6.11

6.08

6.01

105

TC

60.0

54.8

50.6

50.4

60.0

54.7

49.8

50.6

60.0

54.8

50.7

50.0

SHC

33.2

43.8

42.3

50.4

33.2

43.7

41.3

50.6

33.2

43.8

42.0

50.0

kW

6.72

6.61

6.56

6.52

6.72

6.61

6.61

6.52

6.72

6.61

6.58

6.50

115

TC

57.0

51.9

47.3

48.2

57.0

51.9

47.4

47.9

57.0

51.9

47.5

15.8

SHC

32.2

42.7

41.3

46.7

32.2

42.7

40.2

47.9

32.2

42.7

40.3

7.8

kW

7.25

7.15

7.03

7.04

7.25

7.15

7.08

7.09

7.25

7.15

7.07

5.46

601A060 (5 TONS)

Temp (F)

Indoor Air Cfm (std)

Air Temperature Entering Outdoor Coil (F db at 70% rh)

Ent Indoor Coil

-10

0

10

17

20

60

1750

TC

17.98

16.57

23.50

21.59

28.92

26.51

33.54

30.53

35.75

32.24

kW

3.90

4.01

4.13

4.22

4.27

2000

TC

18.38

16.87

23.90

21.89

29.32

26.91

34.04

31.03

36.25

32.64

kW

3.97

4.07

4.18

4.26

4.30

2250

TC

18.78

17.27

24.30

22.29

29.73

27.32

34.34

31.33

36.65

33.04

kW

4.04

4.14

4.23

4.31

4.35

70

1750

TC

16.77

15.36

22.29

20.49

27.92

25.61

32.44

29.63

34.75

31.33

kW

4.14

4.29

4.43

4.53

4.59

2000

TC

17.17

15.77

22.80

20.89

28.32

26.01

32.94

30.03

35.25

31.83

kW

4.22

4.34

4.47

4.57

4.62

2250

TC

17.57

16.17

23.20

21.29

28.82

26.41

33.44

30.53

35.75

32.24

kW

4.29

4.41

4.53

4.62

4.66

80

1750

TC

15.26

14.06

20.99

19.28

26.71

24.60

31.33

28.52

33.54

30.23

kW

4.40

4.57

4.75

4.87

4.93

2000

TC

15.67

14.36

21.49

19.68

27.32

25.01

31.83

29.02

34.14

30.73

kW

4.47

4.63

4.79

4.90

4.95

2250

TC

16.07

14.76

21.89

20.08

27.72

25.41

32.34

29.52

34.65

31.23

kW

4.55

4.70

4.84

4.94

4.99

601A060 (5 TONS)

Temp (F)

Indoor Air Cfm (std)

Air Temperature Entering Outdoor Coil (F db at 70% rh)

Ent Indoor Coil

30

40

47

50

60

60

1750

TC

43.18

37.86

51.52

51.52

57.74

57.74

58.55

58.55

64.97

64.97

kW

4.42

4.59

4.67

4.68

4.76

2000

TC

43.68

38.26

51.92

51.92

58.15

58.15

59.55

59.55

65.98

65.98

kW

4.44

4.59

4.66

4.71

4.79

2250

TC

44.19

38.66

51.92

51.92

58.35

58.35

59.95

59.95

67.08

67.08

kW

4.48

4.60

4.71

4.75

4.86

70

1750

TC

42.28

37.06

50.61

50.61

57.24

57.24

59.15

59.15

64.57

64.57

kW

4.76

4.95

5.10

5.13

5.30

2000

TC

42.88

37.56

51.22

51.22

57.34

57.34

59.55

59.55

65.68

65.68

kW

4.77

4.94

5.06

5.10

5.16

2250

TC

43.38

37.96

51.62

51.62

57.94

57.94

59.55

59.55

66.98

66.98

kW

4.80

4.96

5.07

5.09

5.16

80

1750

TC

41.07

36.05

49.51

49.51

56.44

56.44

58.55

58.55

64.07

64.07

kW

5.13

5.34

5.52

5.57

5.72

2000

TC

41.68

36.55

50.21

50.21

56.94

56.94

58.75

58.75

65.58

65.58

kW

5.13

5.32

5.48

5.51

5.64

2250

TC

42.28

37.06

50.81

50.81

57.14

57.14

59.35

59.35

66.88

66.88

kW

5.16

5.34

5.46

5.50

5.63

Advertising