PERFORMANCE DATA (cont)

ECONOMIZER 1-in. FILTER PRESSURE DROP (in. wg)

MULTIPLICATION FACTORS

Example: 20 kW (at 240v) heater on 230v

= 20.0 (.92 mult factor)
= 18.4 kW capacity at 230 v

LEGEND
BF
—Bypass Factor
Ewb—Entering Wet-Bulb
kW—Total Unit Power Input
SHC—Sensible Heat Capacity (1000 Btuh)
TC—Total Capacity (1000 Btuh) (net)
Edb—Entering Dry-Bulb
rh—Relative Humidity

Indicates Integrated Ratings

UNIT601A

PRESSURE DROP

018-042

0.20

048-060

0.25

HEATER kW

RATING

VOLTAGE

DISTRIBUTION

V/3/60

MULTIPLICATION

FACTOR

240

200
208
230
240

.69
.75
.92

1.00

480

440
460
480

.84
.92

1.00

4. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.

Above 80 F edb, add (corr factor x cfm) to SHC.

Correction Factor = 1.10 x (1 – BF) x (edb – 80).

5. Integrated capacity is maximum (instantaneous) capacity less the effect of frost

on the outdoor coil and the heat required to defrost it.

NOTES:
1. Ratings are net; they account for the effects of the evaporator-fan motor power

and heat.

2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

sensible capacity (Btuh)

t

= t

؊

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air leaving

lwb

evaporator coil (h

)

lwb

total capacity (Btuh)

h

= h

؊

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering evaporator coil

ewb

C00094

Balance Point Worksheet

0

10

20

30

40

50

60

70

-10

0

10

17

20

30

40

47

50

60

Outdoor Air Temp (Deg F)

018
024
030
036
042
048
060

Based on Indoor Entering Air of 70 F and Rated CFM

Building Heat Loss

, 1000BTUH

Unit Integ

rated Heating Capacity (x1000BTUH)

Unit 601A

Advertising