ELECTRICAL DATA

UNIT

SIZE

601A

V-PH-Hz

VOLTAGE

RANGE

COMPRESSOR

OFM

FLA

IFM

FLA

ELECTRIC HEAT

SINGLE POINT POWER SUPPLY

Min

Max

RLA

LRA

Nominal kW*

FLA

MCA

Fuse or Ckt Bkr

MOCP

018

208/230-1-60

187

253

9.0

48

0.9

1.8

—/—

3.8/5.0
5.4/7.2

7.5/10.0

—/—

18.1/20.8
26.0/30.0
36.1/41.7

14.0/14.0
36.5/40.0
46.4/51.5
59.1/66.0

20/20
40/45
50/60



60/70

024

208/230-1-60

187

253

12.8

61

0.9

2.0

—/—

3.8/5.0
5.4/7.2

7.5/10.0

—/—

18.1/20.8
26.0/30.0
36.1/41.7

18.9/18.9
41.5/44.9
51.4/56.4
64.0/71.0

25/25
45/45

60/—


—/70

70/80

030

208/230-1-60

187

253

14.7

82

0.9

2.0

—/—

3.8/5.0
5.4/7.2

7.5/10.0

11.3/15.0

—/—

18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5

21.3/21.3
43.8/47.3
53.8/58.8
66.4/73.4
89.0/99.4

25/25
45/50




70/70
70/80

90/100

208/230-3-60

187

253

9.9

78

0.9

2.0

—/—

3.8/5.0

7.5/10.0

11.3/15.0

—/—

10.4/12.0
20.8/24.1
31.3/36.1

15.3/15.3
28.3/30.3
41.3/45.3
54.4/60.4

20/20
30/35
45/50

60/—



—/70

036

208/230-1-60

187

253

16.8

86

1.5

4.1

—/—

3.8/5.0
5.4/7.2

7.5/10.0

11.3/15.0

—/—

18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5

26.6/26.6
49.2/52.6
59.1/64.1
71.7/78.7

94.3/104.7

35/35
50/60




70/80
80/80

100/110

208/230-3-60

187

253

9.9

78

1.5

4.1

—/—

3.8/5.0

7.5/10.0

11.3/15.0

—/—

10.4/12.0
31.3/36.1
36.1/41.7

18.0/18.0
31.0/33.0
44.0/48.0
57.1/63.1

25/25
35/35
45/50

60/—



—/70

460-3-60

414

506

5.5

40

0.8

1.9

—/—

5

10
15

—/—

6.0

12.0
18.0

9.6

17.1
24.6
32.1

15
20
25
35




042

208/230-1-60

187

253

20.6

115

0.9

3.8

—/—

3.8/5.0
5.4/7.2

7.5/10.0

11.3/15.0
15.0/20.0

—/—

18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3

30.5/30.5
53.0/56.5
62.9/68.0
75.6/82.5

98.1/108.6

120.7/134.6

40/40
60/60





80/90
80/90

100/110
125/150

208/230-3-60

187

253

12.4

90

0.9

3.8

—/—

3.8/5.0

7.5/10.0

11.3/15.0
15.0/19.9

—/—

10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0

20.2/20.2
33.2/35.2
46.3/50.3
59.3/65.3
72.2/80.2

25/25
40/40
50/60

60/—



—/70

80/90

460-3-60

414

506

6.7

45

0.8

1.8

—/—

5

10
15

20.0

—/—

6.0

12.0
18.0
24.1

11.0
18.5
26.0
33.5
41.0

15
20
30
35
45





048

208/230-1-60

187

253

24.4

140

1.5

3.5

—/—

3.8/5.0
5.4/7.2

7.5/10.0

11.3/15.0
15.0/19.9

—/—

18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3

35.5/35.5
58.1/61.5
68.0/73.0
80.6/87.6

103.2/113.6
125.8/139.7

45/45





70/70
90/90

90/100

110/125
150/150

208/230-3-60

187

253

14.1

105

1.5

3.5

—/—

3.8/5.0

7.5/10.0

11.3/15.0
15.0/20.0

—/—

10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0

22.6/22.6
35.7/37.7
48.7/52.7
61.7/67.7
74.6/82.6

30/30
40/40
50/60




70/70
80/90

460-3-60

414

506

7.1

53

0.8

1.8

—/—

5

10
15
20

—/—

6.0

12.0
18.0
24.1

11.5
19.0
26.5
34.0
41.5

15
20
30
35
45





060

208/230-1-60

187

253

28.8

165

1.5

6.2

—/—

3.8/5.0
5.4/7.2

7.5/10.0

11.3/15.0
15.0/20.0

—/—

18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3

43.7/43.7
66.3/69.7
76.2/81.2
88.8/95.8

111.4/121.8
134.0/147.9

60/60





70/80

100/110
100/110
125/125
150/150

208/230-3-60

187

253

19.4

125

1.5

6.2

—/—

3.8/5.0

7.5/10.0

11.3/15.0
15.0/19.9

—/—

10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0

32.0/32.0
45.0/47.0
58.0/62.1
71.1/77.1
83.9/91.9

40/40
50/50




60/70
80/80

90/100

460-3-60

414

506

8.0

63

0.8

3.2

—/—

5

10
15
20

—/—

6.0

12.0
18.0
24.1

14.0
21.5
29.0
36.6
44.1

20
25
30
40
45





*Heater capacity (KW) based on heater voltage of 208v, 240v, & 480v. If power distribution voltage to unit varies from rated heater voltage, heater KW