Performance data (cont) – Bryant 601A User Manual
Page 13

—13—
PERFORMANCE DATA (cont)
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE
-10–20
HEATING EXTENDED PERFORMANCE TABLE 30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 18.
601A030 (2.5 TONS)
Temp (F)
Air Ent
Outdoor Coil
(Edb)
Indoor Entering Air—CFM/BF
875/0.051
1000/0.077
1125/0.107
Indoor Entering Air—Ewb (F)
72
67
63*
62
72
67
63*
62
72
67
63*
62
85
TC
32.6
30.1
27.1
27.0
32.8
30.4
27.5
27.9
32.8
30.5
28.4
27.9
SHC
16.9
21.4
21.4
24.7
17.3
22.5
19.8
22.8
17.6
23.4
22.6
23.8
kW
2.79
2.73
2.63
2.60
2.89
2.84
2.68
2.76
3.02
2.96
2.91
2.87
95
TC
31.3
28.8
26.1
25.7
31.5
29.0
26.4
25.8
31.5
29.1
26.9
25.9
SHC
16.4
21.0
19.2
25.7
16.9
21.9
20.0
22.2
17.3
22.9
22.1
21.9
kW
2.97
2.92
2.84
2.78
3.08
3.03
2.85
2.87
3.21
3.15
3.07
3.03
105
TC
29.9
26.7
24.5
25.0
30.1
27.4
24.9
24.8
30.1
27.5
25.1
23.8
SHC
15.9
20.6
18.8
23.3
16.5
21.4
19.7
23.3
16.9
22.5
21.4
22.4
kW
3.17
3.05
2.97
2.98
3.28
3.20
3.20
3.19
3.41
3.30
3.21
3.17
115
TC
28.3
25.1
23.2
23.2
28.5
25.6
23.1
22.9
28.4
25.7
22.3
22.6
SHC
15.3
19.2
18.6
22.5
15.9
20.6
19.3
21.8
16.4
21.7
21.0
20.6
kW
3.36
3.24
3.15
3.11
3.48
3.36
3.22
3.32
3.61
3.47
3.31
3.54
601A030 (2.5 TONS)
Temp (F)
Indoor Air Cfm (std)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
Ent Indoor Coil
-10
0
10
17
20
60
875
TC
5.66
5.20
9.42
8.65
13.15
12.07
15.63
14.24
16.91
15.23
kW
1.82
1.90
1.99
2.08
2.12
1000
TC
5.81
5.34
9.63
8.85
13.45
12.36
15.82
14.44
17.21
15.53
kW
1.86
1.94
2.02
2.11
2.15
1125
TC
5.94
5.47
9.80
9.00
13.65
12.56
16.02
14.64
17.41
15.72
kW
1.90
1.97
2.05
2.14
2.18
70
875
TC
5.02
4.63
8.74
8.03
12.46
11.47
14.83
13.55
16.12
14.54
kW
1.84
1.94
2.04
2.15
2.20
1000
TC
5.18
4.77
8.94
8.21
12.66
11.67
15.23
13.85
16.52
14.83
kW
1.88
1.98
2.08
2.18
2.23
1125
TC
5.32
4.90
9.13
8.38
12.96
11.87
15.33
13.94
16.61
15.03
kW
1.92
2.02
2.11
2.20
2.24
80
875
TC
4.28
3.95
7.96
7.31
11.67
10.68
14.14
12.86
15.33
13.85
kW
1.86
1.98
2.10
2.21
2.26
1000
TC
4.44
4.08
8.16
7.50
11.87
10.88
14.44
13.15
15.63
14.04
kW
1.90
2.02
2.13
2.24
2.29
1125
TC
4.58
4.21
8.35
7.66
12.07
11.08
14.64
13.35
15.92
14.34
kW
1.94
2.05
2.17
2.28
2.31
601A030 (2.5 TONS)
Temp (F)
Indoor Air Cfm (std)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
Ent Indoor Coil
30
40
47
50
60
60
875
TC
21.26
18.69
25.91
25.91
28.58
28.58
30.86
30.86
33.13
33.13
kW
2.27
2.43
2.50
2.59
2.74
1000
TC
21.66
18.99
26.01
26.01
29.37
29.37
31.15
31.15
34.32
34.32
kW
2.30
2.44
2.53
2.60
2.81
1125
TC
21.95
19.19
26.21
26.21
29.87
29.87
31.45
31.45
35.80
35.80
kW
2.33
2.46
2.57
2.62
2.84
70
875
TC
20.27
17.70
25.22
25.22
28.38
28.38
30.26
30.26
31.84
31.84
kW
2.35
2.54
2.70
2.72
2.92
1000
TC
20.77
18.20
25.61
25.61
29.17
29.17
30.76
30.76
33.13
33.13
kW
2.37
2.56
2.68
2.74
2.94
1125
TC
21.06
18.39
25.81
25.81
29.47
29.47
31.05
31.05
34.81
34.81
kW
2.40
2.58
2.70
2.71
2.95
80
875
TC
19.28
16.91
24.13
24.13
28.38
28.38
29.77
29.77
30.86
30.86
kW
2.43
2.62
2.82
2.87
2.99
1000
TC
19.68
17.21
24.53
24.53
28.58
28.58
30.26
30.26
33.53
33.53
kW
2.46
2.65
2.81
2.88
3.05
1125
TC
19.98
17.50
24.92
24.92
28.88
28.88
30.56
30.56
34.32
34.32
kW
2.48
2.67
2.83
2.90
3.06