SECTION 3 - CHASSIS & TURNTABLE

3121127

– JLG Lift –

3-67

RBS Start

RBS shutdown

Call to start

Manual

48V DC applied to the input

Automatic 1 Low battery voltage (below

48VDC)
2 Low engine temperature
(below 5°C)
3 Low start battery voltage
(below 12.2V)

Engine start time
delay

RBS waits to verify that call to
start is valid (not a transient con-
dition).

Preheat delay

- if engine temperature is below
32°F (0°C)

Crank time
(Rest time)

RBS will crank and rest until
engine starts, or Overcrank fault
is indicated after 3 failed crank
cycles.

Time delay bypass

RBS waits until normal engine
operating conditions are
reached before Low oil pressure
and Underspeed faults are moni-
tored.

Call to start removed Manually

Inhibit run input applied

Automati-
cally:

1 Battery voltage above
54VDC and finish charging cur-
rent below 30ADC
2 Engine temperature above
8°C
3 Start battery voltage above
12.9V and finish charging cur-
rent below 30ADC

Engine run time delay

This period ensures that no fur-
ther call to start conditions
occur prior to cool-down period.

Cool-down period

Alternator output is reduced to a
minimal level to allow the engine
to cool down.