Alarms and fault flash codes, Generator system flash codes -56 – JLG M450 ANSI Service Manual User Manual

Page 96

Advertising
background image

SECTION 3 - CHASSIS & TURNTABLE

3-56

– JLG Lift –

3121127

To Connect the JLG Control System Analyzer
to the Generator

The JLG Control System Analyzer can be used to monitor
generator settings and conditions. Connect the analyzer
as follows:

1. Connect the four pin end of the cable supplied with

the analyzer, to the connector behind the ground
control module located on the left side of the
machine next to the ground control station and con-
nect the remaining end of the cable to the analyzer.
The ground control module contains the settings for
the generator.

NOTE: The cable has a four pin connector at each end of

the cable; the cable cannot be connected back-
wards.

2. Power up the Analyzer by pulling out the ground sta-

tion EMS and positioning the Generator Enable
switch on the platform control box to the "on" posi-
tion. Refer to Figure 3-21., Generator System Ana-
lyzer Flow Chart

Alarms and Fault Flash Codes

In the event of an RBS alarm, a flash code will be issued
and an alarm indicated on the analyzer.

NOTE: Alarms must be reset once the fault has been cor-

rected.

• Low Oil Pressure

Enabled once TDBP (time delay bypass) period has
elapsed after engine startup. If the low engine oil pressure
switch closes, the engine will stop immediately and a low
oil pressure alarm will be indicated.

• High Engine Temperature

If the engine oil temperature exceeds the high engine tem-
perature setting, the engine will stop immediately and a
low oil pressure alarm will be indicated.

Table 3-8. Generator System Flash Codes

Code

Alarm

Description

1-1

Low Oil Pressure

Shutdown due to low engine
oil pressure

1-2

High Engine Tem-
perature

Shutdown due to high engine
oil temperature

1-3

Engine Overspeed

Shutdown due to high engine
speed

1-4

E n g i n e U n d e r-
speed/Overcrank

Shutdown due to engine
overcrank or underspeed

1-5

No Speed Signal

Shutdown due to loss of
speed signal

2-1

Overvoltage

Shutdown due to high output
voltage

2-2

E n g i n e S t a r ti n g
System fault

Alarm not a shutdown; Indi-
c a t e s p r o b l e m w i t h t h e
engine starting system

2-3

Not Used

Not Used

2-4

L o s s o f Vo l ta g e
Sense

Shutdown due to loss of volt-
age sensing

Contin-

uous

Unit Disabled

No Faults. RBS enabled and
can respond to any CTS

Off

Unit Disabled

RBS off or disabled; Will not
respond to any CTS