Warning, Caution – Bryant 312AAV/JAV User Manual

Page 20

Advertising
background image

20

115-VOLT FIELD-

SUPPLIED

FUSED

DISCONNECT

JUNCTION

BOX

CONTROL

BOX

24-VOLT

TERMINAL

BLOCK

THREE-WIRE

HEATING-

ONLY

FIVE

WIRE

NOTE 2

NOTE 1

1-STAGE

THERMOSTAT

TERMINALS

FIELD-SUPPLIED

FUSED DISCONNECT

CONDENSING

UNIT

FURNACE

COM

R

W

C

Y

R

G

GND

GND

FIELD 24-VOLT WIRING

FIELD 115-, 208/230-, 460-VOLT WIRING

FACTORY 24-VOLT WIRING

FACTORY 115-VOLT WIRING

Connect Y/Y2-terminal as shown for proper operation.

Some thermostats require a "C" terminal connection as shown.

If any of the original wire, as supplied, must be replaced, use

same type or equivalent wire.

208/230- OR

460-VOLT

THREE

PHASE

208/230-

VOLT

SINGLE

PHASE

WHT

BLK

WHT

BLK

W/W1

W2

Y/Y2

G

NOTES: 1.

2.

3.

A95236

Fig. 23 -- Field Wiring Diagram

A 1/8--in. (3 mm) NPT plugged tapping, accessible for test gauge
connection, MUST be installed immediately upstream of gas

supply connection to furnace and downstream of manual
equipment shutoff valve.
Piping should be pressure and leak tested in accordance with

NFGC in the United States, local, and national plumbing and gas
codes before the furnace has been connected. After all

connections have been made, purge lines and check for leakage at
furnace prior to operating furnace.
If pressure exceeds 0.5 psig (14--In. W.C.), gas supply pipe must

be disconnected from furnace and capped before and during
supply pipe pressure test. If test pressure is equal to or less than

0.5 psig (14--In. W.C.), turn off electric shutoff switch located on
furnace gas control valve and accessible manual equipment

shutoff valve before and during supply pipe pressure test. After

all connections have been made, purge lines and check for
leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and
minimum inlet supply pressures marked on the rating plate with

the furnace burners ON and OFF.
ELECTRICAL CONNECTIONS

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Blower access panel door switch opens 115--v power to

control. No component operation can occur. Do not bypass

or close switch with panel removed.

!

WARNING

See Fig. 23 for field wiring diagram showing typical field 115--v
wiring. Check all factory and field electrical connections for

tightness.
Field--supplied wiring shall conform with the limitations of 63_F

(33_C) rise.

ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal

injury, death, or property damage.
The cabinet MUST have an uninterrupted or unbroken

ground according to NEC ANSI/NFPA 70--2008 or local

codes to minimize personal injury if an electrical fault

should occur. This may consist of electrical wire, conduit

approved for electrical ground or a listed, grounded power

cord (where permitted by local code) when installed in

accordance with existing electrical codes. Refer to the

power cord manufacturer’s ratings for proper wire gauge.

Do not use gas piping as an electrical ground.

!

WARNING

FURNACE MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent

furnace operation.
Furnace control must be grounded for proper operation or

else control will lock out. Control must remain grounded

through green/yellow wire routed to gas valve and manifold

bracket screw.

CAUTION

!

115--V WIRING
Verify that the voltage, frequency, and phase correspond to that

specified on unit rating plate. Also, check to be sure that service
provided by utility is sufficient to handle load imposed by this

equipment. Refer to rating plate or Table 7 for equipment
electrical specifications.

312AA

V

Advertising