Warning, Caution – Bryant 312AAV/JAV User Manual

Page 34

Advertising
background image

34

Table 10 – 2--Stage Furnace Setup Switch Description

SETUP

SWITCH NO.

SWITCH

NAME

NORMAL

POSITION

DESCRIPTION

OF USE

SW---1

Adaptive Heat Mode

OFF

When OFF, allows 2---stage operation with a single stage thermostat.

Turn ON when using 2 stage thermostat to allow Low Heat operation

when R to W/W1 closes and High Heat operation when R to W/W1

and W2 close.

SW---2

Blower OFF delay

ON or OFF

Control blower OFF delay time. Used in conjunction with SW---3.

See Table 14.

SW---3

Blower OFF delay

ON or OFF

Control blower OFF delay time. Used in conjunction with SW---2.

See Table 14.

Step 2 — Start--Up Procedures

FIRE AND EXPLOSION HAZARD
Failure to follow this warning could cause personal injury,

death and/or property damage.
Never test for gas leaks with an open flame. Use a

commercially available soap solution made specifically for

the detection of leaks to check all connections.

!

WARNING

1. Purge gas lines after all connections have been made.
2. Check gas lines for leaks.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury, or death.
Blower access door switch opens 115--v power to control.

No component operation can occur unless switch is closed.

Caution must be taken when manually closing this switch

for service purposes.

!

WARNING

3. To Begin Component Self--Test:

Remove blower access door. Disconnect the thermostat R
lead from furnace control board. Manually close blower
door switch. Short (jumper) the COM--24v terminal on

control to the TEST/TWIN 3/16--in. (8 mm) quick--con-
nect terminal on control until the LED goes out (approx-

imately 2 sec). Gas valve and humidifier will not be turned
on. Remove jumper from terminals. (See Fig. 33 and
Table 10.)

NOTE: The furnace control allows all components, except the
gas valve, to be run for short period of time. This feature helps
diagnose a system problem in case of a component failure.
Component test feature will not operate if any thermostat signal is
present at the control.
Refer to service label attached to furnace or See Fig. 51.
Component test sequence is as follows:

a. LED will display previous status code 4 times.

b. Inducer motor starts on high--speed and continues to run

until Step g of component test sequence.

c. Hot surface igniter is energized for 15 sec., then off.

d. Blower motor operates on LO--HEAT speed for 10 sec.

e. Blower motor operates on HI--HEAT speed for 10 sec.

f. Blower motor operates on COOL speed for 10 sec.

g. Inducer motor goes to low--speed for 10 sec., then stops.
h. Reconnect R lead to furnace control board, remove tape

from blower door switch and re--install blower door.

4. Operate furnace per instruction on inner door.

5. Verify furnace shut down by lowering thermostat setting

below room temperature.

6. Verify furnace restarts by raising thermostat setting above

room temperature.

Step 3 — Adjustments

FIRE HAZARD
Failure to follow this warning could result in injury, death

and/or property damage.
DO NOT bottom out gas valve regulator adjusting screw.

This can result in unregulated manifold pressure and result

in excess over--fire and heat exchanger failures.

!

WARNING

UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace

life.
DO NOT re--drill orifices. Improper drilling (burrs, out--of

round holes, etc.) can cause excessive burner noise and

misdirection of burner flames. This can result in flame

impingement of heat exchangers, causing failures.

CAUTION

!

Furnace gas input rate on rating plate is for installations at

altitudes up to 2000 ft. (610 M). Furnace input rate must be
within +/--2% of furnace rating plate input. For altitudes above

5500 ft. (1676 M), a field--supplied high altitude pressure switch
is required.

1. Determine the correct gas input rate.

The input rating for altitudes above 2,000 ft. (610 M) must

be reduced by 4% for each 1,000 ft. (305 M) above sea
level.

For installations below 2000 ft. (610 M), refer to the unit
rating plate.
For installations above 2000 ft. (610 M), multiply the in-

put on the rating plate by the derate multiplier in Table 11
for the correct input rate.

2. Determine the correct orifice and manifold pressure adjust-

ment. All models in all positions except Low NOx models
in downflow and horizontal positions use Table 15

(22,000 BTUH per burner).

312AA

V