Warning, Caution – Bryant 312AAV/JAV User Manual

Page 44

Advertising
background image

44

SERVICE AND MAINTENANCE

PROCEDURES

FIRE, PERSONAL INJURY AND UNIT DAMAGE

HAZARD
Failure to follow this warning could result in personal injury,

death and/or property damage.
The ability to properly perform maintenance on this

equipment requires certain knowledge, mechanical skills,

tools, and equipment. If you do not possess these, do not

attempt to perform any maintenance on this equipment other

than those procedures recommended in the User’s Manual.

!

WARNING

ELECTRICAL SHOCK, FIRE OR EXPLOSION

HAZARD
Failure to follow this warning could result in personal injury

or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF position and

install a lockout tag.

There may be more than one

disconnect switch. Lock out and tag switch with a suitable

warning label. Verify proper operation after servicing.

!

WARNING

UNIT OPERATION HAZARD
Failure to follow this caution may result in improper unit

operation or failure of unit components.
Label all wires prior to disconnection when servicing

controls. Wiring errors can cause improper and dangerous

operation.

CAUTION

!

ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental

pollution.
Remove and recycle all components or materials (i.e. oil,

refrigerant, control board, etc.) before unit final disposal.

CAUTION

!

Step 1 — Introduction

GENERAL
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the

blower is located below the combustion and controls section of

the furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 4,

you must revise your orientation to component location
accordingly.

ELECTRICAL CONTROLS AND WIRING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
There may be more than one electrical supply to the

furnace. Check accessories and cooling unit for additional

electrical supplies that must be shut off during furnace

servicing. Lock out an tag switch with a suitable warning

label.

!

WARNING

The electrical ground and polarity for 115--v wiring must be
properly maintained. Refer to Fig. 23 for field wiring information

and to Fig. 52 for furnace wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
control will flash rapidly and prevent the furnace from heating.
The control system also requires an earth ground for proper
operation of the control and flame--sensing electrode.
The 24--v circuit contains an automotive--type, 3--amp. fuse
located on the control. (See Fig. 31.) Any shorts of the 24--v

wiring during installation, service, or maintenance will cause this

fuse to blow. If fuse replacement is required, use ONLY a 3--amp.
fuse. The control LED will display status code 24 when fuse

needs to be replaced.
Proper instrumentation is required to service electrical controls.

The control in this furnace is equipped with a Status Code LED

(Light--Emitting Diode) to aid in installation, servicing, and
troubleshooting. Status codes can be viewed at the sight glass in

blower access door. The furnace control LED is either ON
continuously, rapid flashing, or a code composed of 2 digits. The

first digit is the number of short flashes, the second digit is the

number of long flashes.
For an explanation of status codes, refer to service label located

on blower access door or Fig. 51, and the troubleshooting guide
which can be obtained from your distributor.
See Fig. 56 for a brief Troubleshooting guide.
For Controls with an Amber LED
The stored status codes will NOT be erased from the control
memory, if 115-- or 24--v power is interrupted. The control will

store up to five (5) status codes.

1. To retrieve status codes, proceed with the following:

NOTE: NO thermostat signal may be present at control, and all
blower--OFF delays must be completed.

a. Leave 115--v power to furnace turned on.

b. Remove outer access door.

c. Look into blower access door sight glass for current LED

status.

d. BRIEFLY remove insulated terminal wire from the draft

safeguard (DSS) switch until LED goes out, then recon-
nect it.

NOTE: If wire to DSS is disconnected longer than 4 sec, main
blower starts, and retrieval request is ignored.

2. When above items have been completed, the LED flashes

status code 4 times. Record this status code for further
troubleshooting. After the LED flashes status code four
times, BRIEFLY remove wire again from DSS switch un-

til LED goes out, then reconnect it to retrieve previous
status code (if available). Repeat as needed for more previ-

ous status codes or until Code 11 appears.

312AA

V

Advertising