gas. This furnace is not approved for installation in mobile
homes, recreational vehicles, or outdoors.
These furnaces shall not be installed directly on carpeting, tile, or
any other combustible material other than wood flooring. For

downflow installations, a factory accessory floor base must be

used when installed on combustible materials and wood flooring.
This special base is not required when this furnace is installed on

the manufacturer’s coil assembly, or when the manufacturer’s coil
box is used. See Fig. 2 for clearance to combustible material

information.
This furnace is designed for minimum continuous return--air
temperature of 60_F (16_C) db or intermittent operation down to

55_F (13_C) db such as when used with a night setback
thermostat. Return--air temperature must not exceed 80_F (27_C)

db. Failure to follow these return--air temperature limits may
affect reliability of heat exchangers, motors, and controls. (See

Fig. 3.)
For accessory installation details, refer to the applicable
instruction literature.
NOTE: Remove all shipping brackets and materials before
operating the furnace.

A10269