Calibration (calibrat) – APG LPU-2428 user manual User Manual
Page 25
![background image](/manuals/554667/25/background.png)
Rev. A3, 11/08
LPU-2428
25
Automation Products Group, Inc.
APG...Providing tailored solutions for measurement applications
Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]
0.00 – 25.00 ft (Distance/Level)
Default: 1.00 ft
Maximum (Max) mA Setpoint (MaxMaSet)
Sets the maximum mA distance, level, volume, or flow.
0.00 – 25.00 ft (Distance/Level)
Default: 25.00 ft
Fail Safe (FailSafe)
Determines the output condition of the sensor in the event of a Loss of
Echo.
Hold, 3.8 mA, 22 mA
Default: Hold
Fail Safe Delay (FS Delay)
Sets the delay in seconds before the sensor will output a Fail Safe
condition.
15 – 9999 Seconds
Default: 15 Seconds
Calibration (Calibrat)
Min mA Value (MinMaVal)
Limits the low end of the mA output.
4.00 – Max mA Value
Default: 4.00
Zero Point
Max. Distance
Zero Point
Max. Distance
20 ma
4 ma
4 ma
20 ma
4ma
set point
20ma
Set Point
4ma
set point
20ma
Set Point