Click Basic Setup.
Select Units to Feet.
Set Application to Volume.
Select Volume Units to Gallons.
Press Send to save (Wait until progress bar completes).

Click App. setup.
Set Tank Type to SCTWBH (Standing Cylindrical Tank with Hemispherical
Bottom).
Set Full Distance to 1 ft.
Set Empty Distance to 10 ft.
Set Tank Diameter to 3 ft. and set Radius of Hemi. to 0 ft.