Wire the burner — rm7897c primary control, Wire the burner – Carlin 702G/O Inst Manual User Manual

Page 16

Advertising
background image

Model 702G/O Advanced gas/oil burners — Instruction manual

Carlin part number MN702GO Rev. 06/23/14

– 16 –

Where appliance instructions differ from this manual, follow the appliance instructions.

Figure 13

702G/O burner wiring using Honeywell RM7897C primary control (see appliance manual or separate wiring information for
burner equipped with a primary control not covered in this manual); see Figure 12 for a legend to callouts.

5. Wire the burner — RM7897C primary control

Wire the burner

(RM7895C or RM7897C primary control only)

1. All wiring must comply with:

In the U.S. — the National Electrical Code, ANSI Z223.1/NFPA 54.

In Canada — the Canadian Electrical Code Part 1, CSA standard C22.1.

All applicable local codes/standards.

2. Connect the burner following Figures 13 and 14 and any special instructions

or wiring diagrams provided with the appliance, burner or other components.

3. The burner requires a 120 VAC/60 hz/single-phase control power supply, with

a 10-amp fuse. The control circuit current draw is approximately 1.2 amps. An

additional power source is required for the motor (120 VAC or 208-220 VAC,

60 hz), with fuse sized accordingly. See Figure 14 for field wiring connections.

4. Read the Honeywell RM7897C instructions for information on setting a room

thermostat, if used.

5. Make sure the burner and appliance are correctly wired and the line switch

is properly fused for the load.

Turn off power to appliance when servicing burner.

Failure to comply could result in severe person-

al injury, death or substantial property damage.

Figure 12

Legend for Figures 13 and 14

Advertising