Step 6, Adjust the burner using test instruments, Step 7 – Carlin 702G/O Inst Manual User Manual

Page 23: Set butterfly gas valve linkage, Verify operation

Advertising
background image

Model 702G/O Advanced gas/oil burners — Instruction manual

Carlin part number MN702GO Rev. 06/23/14

– 23 –

Where appliance instructions differ from this manual, follow the appliance instructions.

Step 6

(firing on gas)

Set butterfly gas valve linkage

1.

Switch the low-fire switch to low fire.

2.

Check CO

2

and CO. The CO

2

should be between 9.0% and 10.0% (natural

gas) or between 10.0% and 11.2% (propane); with CO less than 100 PPM.

3.

To adjust the low-fire air (change CO

2

), move the burner fuel selector

switch to OFF. Adjust the butterfly gas valve linkage as described in

the following to change the low-fire gas flow to the burner head. Do not

change the main gas pressure regulator setting.

4.

DO NOT ADJUST THE LOW-FIRE AIR DAMPER SETTING. This must

be left as set for oil firing.

5.

See Figure 18 for location of linkage components.

Figure 18

Butterfly gas valve linkage

6.

Raise the damper motor linkage by pulling up on the damper linkage

locknut and hold in this position.

7.

Loosen the two hex head screws on the butterfly valve linkage arm boss.

Then lower the damper linkage to the low fire position with the damper

linkage locknut. Release the locknut.

8.

Mark the position of the butterfly valve linkage arm swivel joint locknut

with a pencil or felt-tip pen. Then loosen the swivel joint locknut.

To adjust the linkage, move the swivel joint locknut in small

increments. A 1/8-inch move can cause CO

2

to change as

much as 1.5%.

If more gas is needed (to increase CO

2

), move the swivel joint to the RIGHT.

If less gas is needed (to decrease CO

2,

), move the swivel joint to the LEFT.

9.

Tighten the swivel joint in place.

10.

Raise the damper motor linkage by pulling up on the damper linkage

locknut and hold in this position. The butterfly valve shaft slot must

be horizontal. If not, use a common-bit screwdriver to rotate the valve

slot to horizontal.

11.

Tighten the two hex head screws on the butterfly valve linkage arm boss.

Then lower the damper motor linkage to the low fire position.

12.

Restart and repeat as necessary until CO

2

and CO are acceptable.

8. Adjust the burner using test instruments

(continued)

Step 7

(firing on oil and on gas)

Verify operation

Burner/appliance/controls operation

Test operating and limit controls on appliance as specified in appliance

instructions.

Check operation of the primary control by forcing lockout to occur. For

primary controls that enter latch-up after multiple lockouts, force latch-up

to occur as well. Reset primary control per control data sheet instructions

after each test.

Start and stop the burner several times, allowing the primary control to

sequence through normal operation. Verify correct operation of burner

and primary control throughout on both oil and gas.

Confirm and/or adjust overfire combustion pressure for oil and gas opera-

tion. Refer to boiler/furnace manufacturer’s recommendations.

Verify vent system operation

Verify vent is operating correctly and flue products are properly exhausted

from building. If the building contains any exhaust fans or conditions that

could affect vent performance, check burner/appliance/vent operation

with exhaust fans (or other conditions) operating.

Combustion/ventilation air

Verify combustion/ventilation air openings are not, and will not be ob-

structed.

Verify air opening louvers are fully open.

If louvers are motor-operated, verify motor and end switch are interlocked

with appliance/burner wiring to prevent operation of the burner if the air

louvers are not fully opened.

Prepare burner for normal operation

Cycle burner off with appliance controls.

Turn off power to the appliance.

Seal the appliance flue test opening.

Verify all components and wires are in place and burner is ready for

operation.

Restore power to the appliance.

Train the user

Train the user to operate the burner and appliance under normal condi-

tions.

Explain the procedure to shut down the burner/appliance when required.

Review the back cover of this manual (and the appliance manual) with

the user.

Verify the user is aware of all procedures specified in the manuals.

Verify that the user will not store or use combustible liquids or materials

or contaminants in the vicinity of the burner/appliance.

Advertising