Set burner initial head and damper positions, Before firing the burner, Determining final adjustments – Carlin 702G/O Inst Manual User Manual

Page 19: Set combustion head (dimension “a”), Set air damper (low fire position)

Advertising
background image

Model 702G/O Advanced gas/oil burners — Instruction manual

Carlin part number MN702GO Rev. 06/23/14

– 19 –

Where appliance instructions differ from this manual, follow the appliance instructions.

Before firing the burner . . .

Set combustion head (Dimension “A”)

1.

The combustion head adjusting screw is used to set the spacing between

the retention ring and throttle ring (or air cone), regulating how much air

passes around the retention ring.

2.

See Figure 16. Loosen the two housing cover screws. Then rotate the

head adjusting screw until the distance from the housing detent to the

beginning of the scale equals the value given in Table 5 (Dimension “A”).

Tighten the housing cover screws.

Set air damper (low fire position)

1.

See Figure 17. Loosen the air damper adjusting screw and locknut.

Rotate the adjusting screw until the air opening between the damper and

the damper housing equals the initial low-fire opening in Table 5. Leave

screw and locknut loose until final adjustment.

Determining final adjustments

1.

The burner is now adjusted to the

approximate

air settings for the firing

rate used. Follow the procedures on the following pages to use test

instruments and make final burner adjustments.

Figure 17

Set initial low fire air damper setting

Figure 16

Set initial combustion head position

Low-fire input

High-fire input

Combustion

head position

Dimension “A”

Air damper

low-fire

opening

Butterfly valve

open – low fire

(factory set)

#2 Fuel oil

Natural gas

#2 Fuel oil

Natural gas

GPH @ 100 PSIG

(Nozzle rating)

MBH

GPH @ 300 PSIG

MBH

Inches

(approximately)

Inches

(approximately)

%

(approximately)

3.50

490

6.00

840

0

3/8

50

3.75

525

6.50

910

1/16

3/8

50

4.00

560

6.90

966

1/8

7/16

50

4.50

630

7.80

1092

3/16

7/16

50

5.00

700

8.70

1218

3/8

1/2

50

5.50

770

9.50

1330

5/8

1/2

50

6.00

840

10.40

1456

1-1/8

9/16

50

6.50

910

11.20

1568

1-3/8

9/16

50

Nozzle specifications:

Standard

Hago 45° SS

Alternates

Hago 45° P

Monarch 45° PLP

Table 5 Initial burner settings (see the pages 20 through 21 for final adjustments using test instruments)

7. Set burner initial head and damper positions

Follow the procedures given here and on the follow-

ing pages to ensure the burner is correctly adjusted.

Take your time and the results in both gas and oil

modes should result in good operation, and avoid

return service calls.

You must perform the adjustments in the sequence

given in this manual.

Failure to follow the correct procedures could re-

sult in severe personal injury, death or substantial

property damage.

Advertising