Checkout procedure — before starting the burner, Before firing the burner, Checklist before firing – Carlin 702G/O Inst Manual User Manual

Page 18

Advertising
background image

Model 702G/O Advanced gas/oil burners — Instruction manual

Carlin part number MN702GO Rev. 06/23/14

– 18 –

Where appliance instructions differ from this manual, follow the appliance instructions.

6. Checkout procedure — before starting the burner

Before firing the burner . . .

Should overheating or an emergency occur, immediately

do the following:

• Shut off oil supply line and gas supply valves.

• Under some circumstances power should remain

on for water pumps or blowers. Determine proper
response before attempting start-up.

• If burner fails ignition on several attempts, use burner

blower to purge appliance chamber before restart.

Checklist before firing . . .

❏

Burner and appliance installed per this manual and appliance
instruction manual?

❏

Burner/appliance installed per all applicable codes?

❏

Installation site has adequate combustion/ventilation air openings
and vent system?

❏

Are voltages correct? Burner, appliance and motor correctly wired
per burner and appliance manuals and wiring diagrams?

❏

Gas manifold spud orifices (on gas manifold, item 29, page 5) sealed
with pipe dope and tight?

❏

Burner nozzle verified per appliance manufacturer’s instructions,
Carlin OEM Spec Guide or Table 1, page 4?

❏

Gas and oil supply lines in good condition, sized and designed
correctly?

❏

Gas and oil line connections and fittings tight?

❏

Oil tank has oil, and oil line valves are open. Oil supply and return
lines purged?

❏

Burner, appliance and all components inspected and in good
condition?

❏

Appliance limit and operating controls properly installed, wired and
adjusted?

❏

Boiler water supply, feed pumps, automatic feeders, and low water
cut-offs properly piped and wired?

❏

Breeching, draft regulator, draft inducer (if required) properly in-
stalled and operational?

❏

Gas train piping and components correctly installed, tested and
verified gas tight?

❏

Vent lines installed when required?

❏

Gas lines purged?

❏

Sufficient gas line pressure present?

Advertising