Appendix A PASSIVE SONAR METER SPECIFICATIONS

A1

Physical Specifications

A1.1

Power Requirements

AC Version: 100 to 240 Volts AC, 50/60 Hz, 25 watts

DC Version: 18-36 Volts DC, 25 watts

Transmitter is rated for transient overvoltage Category II.

A1.2

Fuse Protection

Fuse replacement should be performed only by trained service
personnel using the proper replacement fuse (defined below) and only
after removing power from the Transmitter. Proper fuse replacement
is an electrical shock and fire hazard issue in ordinary locations as
well as an explosion hazard issue in hazardous (classified) locations.

WARNING

Explosion Hazard - Do not remove or replace fuses unless power
has been disconnected or the area is known to be free of
ignitable concentrations of flammable gases or vapors.

AVERTISSEMENT

Risque d’Explosion – Couper le courant ou s’assurer que
l’emplacement est désigné non dangereux avant de replacer les
fusibles.

WARNING

Explosion Hazard - Repair and replacement of internal cabling,
circuit boards, or components on circuit boards should only be
performed using factory-approved replacement components and
procedures. Unauthorized repairs may impair suitability for
Division 2.

AVERTISSEMENT

Risque d’Explosion – La substitution de composants peut rendre
ce matériel inacceptable pour les emplacements de classe i,