10.3 Requirements for connection cables

Caution!

Risk of damage to equipment or malfunctions as a result of incorrect connec-
tion cables.

Ì

On the usage of other connection components, the requirements in the fol-
lowing table apply. EUCHNER provides no warranty for safe function in case
of failure to comply with these requirements.

Observe the following requirements with respect to the connection cables:

Parameter

Value

Unit

Wire cross-section min.

0.13

mm²

R max.

60

W

/km

C max.

120

nF/km

L max.

0.65

mH/km

10.4 Notes on cable laying

Ì

Lay all MGB connection cables in a common cable harness.

Important: lay cables in a common harness

Figure 15: Stipulated cable laying

PLC

+ 24 V DC

cabinet

0 V

MGB-L.-...

FI1A/

FI1B

FO1A/

FO1B

UB 0V UA 0V