Deactivating guard lock monitoring

Warning!

Risk of injury due to inactive guard lock monitoring.

Ì

If guard lock monitoring is inactive, the position of the guard locking does
not influence the safety outputs. The safety guard can be opened immediate-
ly. This setting is not allowed to be used in applications in which, e.g., there
is hazard due to overrunning machinery movement.

1. Switch off power supply.
2. Set DIPswitches 3-5 as shown.

Deactivating guard lock monitoring

Activating guard lock monitoring

1

ON

2

3 4 5

6

1

ON

2

3 4 5

6

3. Switch the power supply on for at least 5 seconds.

¨

The change is confirmed by the illumination of the Power LED. All other LEDs

are off.

4. Switch off power supply and set DIPswitch 5 to OFF.

¨

The next time the device is started, it operates in the operating mode set.