Operating Instructions MGB-L1...AR.-... / MGB-L2...AR.-... and MGB-L1...AP.-... / MGB-L2...AP.-...
Deactivating guard lock monitoring
Warning!
Risk of injury due to inactive guard lock monitoring.
Ì
If guard lock monitoring is inactive, the position of the guard locking does
not influence the safety outputs. The safety guard can be opened immediate-
ly. This setting is not allowed to be used in applications in which, e.g., there
is hazard due to overrunning machinery movement.
1. Switch off power supply.
2. Set DIPswitches 3-5 as shown.
Deactivating guard lock monitoring
Activating guard lock monitoring
1
ON
2
3 4 5
6
1
ON
2
3 4 5
6
3. Switch the power supply on for at least 5 seconds.
¨
The change is confirmed by the illumination of the Power LED. All other LEDs
are off.
4. Switch off power supply and set DIPswitch 5 to OFF.
¨
The next time the device is started, it operates in the operating mode set.