Operating Instructions MGB-L1...AR.-... / MGB-L2...AR.-... and MGB-L1...AP.-... / MGB-L2...AP.-...
Activating release monitoring
Important!
Release monitoring can be activated only if guard lock monitoring is also active.
Note!
When release monitoring is active, the system enters into a latching fault when
the escape release or mechanical release is actuated.
See System status table, signal sequence incorrect status (DIA red, Lock flashes
1 time).
1. Switch off power supply.
2. Set DIPswitches 5 and 6 as shown.
Deactivating release monitoring
Activating release monitoring
1
ON
2 3 4
5 6
1
ON
2 3 4
5 6
3. Switch on power supply for 5 s.
¨
The change is confirmed by the illumination of the Power LED. All other LEDs
are off.
4. Switch off power supply and set DIPswitch 5 to OFF.
The next time the device is started, it operates in the operating mode set.