Specifies the behavior for the Value for states other than Valid.

Safe State

0
1
2
3

Zero
Full Scale
Hold last value
Use safe value

Safe Value: The value to be used for Safe State = Safe Value.




Index

SI

DataType

NV Access PM Name

6000 0x0E

BOOL RO tx

TxPdoState

0x11

REAL

RO

tx

Sensor

Value

Is set if the device is not in Safe State (value (I 0x6nn0, SI 0x11) = valid)

TxPdoState

0
1

Invalid
Valid

The corrected, converted, calibrated final analog input value of the sensor.

Index

SI

DataType

NV Access PM Name

6001 0x01

BOOL RO tx

Reading

Valid

0x02

BOOL

RO

tx

Overrange

Exceeded

0x03

BOOL

RO

tx

Underrange

Exceeded

Indicates whether the Value parameter contains a valid value within the specified
accuracy or not.

Reading Valid

0 Invalid
1 Valid


Indicates whether the Value parameter contains a value in over range.

Reading Valid

0

No Overrange Exceeded

1 Overrange

Exceeded


Subindex 0x01

Subindex 0x02

4.4 Input Area PCG with

ATM (0x6000…0x6FFF)

4.4.1 Input Common

Subindex 0x0E

Subindex 0x11

4.4.2 Input Capacitance

Diaphragm

Subindex 0x01

Subindex 0x02