9 term definition – JUMO 902931 Wtrans Receiver with Wireless Data Transmission Operating Manual User Manual
Page 69

69
9 Term definition
Measuring circuit monitoring of the analog outputs
Underrange:
- Current output 4 to 20 mA
- Current output 0 to 20 mA
- Voltage output 0 to 10 V
Dropping to 3.8 mA,
then jump to the configured signaling
Dropping to -0.1 mA,
then jump to the configured signaling
Dropping to -0.1 V,
then jump to the configured signaling
Overrange:
- Current output 4 to 20 mA
- Current output 0 to 20 mA
- Voltage output 0 to 10 V
Rising to 20.5 mA,
then jump to the configured signaling
Rising to 20.5 mA,
then jump to the configured signaling
Rising to 10.25 V,
then jump to the configured signaling
Probe short circuit or
probe/cable break
and alarms:
- Current output 4 to 20 mA
- Current output 0 to 20 mA
- Voltage output 0 to 10 V
Positive signaling: > 21.6 mA
Negative signaling: < 3.6 mA
Positive signaling: > 21.6 mA
Negative signaling: < -0.1 mA
Positive signaling: > 10.5 V
Negative signaling: < -0.1 V
Output behavior
The output behavior (positive or negative signaling) can be con-
figured.