FEaTURE DETaILS

ET200

Instruction Manual

GENERaL SPECIFICaTIONS

The Klein Tools ET200 is a solid-state electrical tester. It measures AC/DC

voltage, tests continuity, and features a bright LED worklight.

Voltage Level Indicators:

12, 24, 48, 120, 208, 240, 277, 480, 600

Voltage Type Indicators:

AC, DC Positive, DC Negative

aC Frequency:

45Hz to 66Hz

Maximum Voltage To Earth Ground:

600V RMS

Maximum Measurable Voltage:

600V RMS (displayed by LEDs)

Input Impedance:

15k

Ω

on connection, up to 150k

Ω

steady-state.

Continuity:

< 270k

Ω

Usage Duty Cycle (above 277V):

1 minute on, 5 minutes off

accuracy:

70% to 100% of indicated voltage

battery Type:

3 x AAA

Operating altitude:

2000m

Relative Humidity:

0°C to 30°C (32°F to 86°F) 90%

30°C to 40°C (86°F to 104°F) 75%

40°C to 55°C (104°F to 131°F) 45%

Operating Temperature:

0°C to 55°C (32°F to 131°F)

Storage Temperature:

0°C to 55°C (32°F to 131°F)

Dimensions:

7.375 x 2.375 x 1.25”

Weight:

8.1oz.

Safety:

CSA C22.2-1010.1, IEC 61010-1, Pollution Degree II

CaT Rating:

CAT IV 600V, CAT III 1000V

WaRNINGS

To ensure safe operation and service of the tester, follow these instructions.

Failure to observe these warnings can result in severe injury or death.

• Before each use, verify meter operation by measuring

a known voltage or current.

• Never use the meter on a circuit with voltages that exceed the

category based rating of this meter.

• Do not use the meter during electrical storms, or in wet weather.
• Do not use the meter or test leads if they appear to be damaged.
• Ensure meter leads are fully seated, and keep fingers away from

the metal probe contacts when making measurements.

• Do not open the meter to replace batteries while the probes

are connected to a voltage source.

• Use caution when working with voltages above 60V DC,

or 25V AC RMS. Such voltages pose a shock hazard.

• Shut off and lock out power before testing continuity.
• Always adhere to local and national safety codes. Use individual

protective equipment to prevent shock and arc blast injury where

hazardous live conductors are exposed.

Indicators

Lights

• LEDs light up numerical voltage level indicators,

as well as AC and DC

+

or DC

indicators.

• Continuity LED will light up on detection.
• Voltage detection will function without batteries installed.

Vibration

• Instrument will vibrate in the presence of voltage

measurements greater than 48V.

• Vibration will function only with batteries installed.

Sound

• Instrument will emit a tone in the presence of voltage

measurements greater than 48V.

• Instrument will emit a tone on detection of continuity.
• Sound will function only with batteries installed.

accuracy
Accuracy of indicator lights is 70% to 100% of the voltage displayed

to account for normal variations in supply voltage.

Worklight
Press the light bulb button above the Klein Tools logo to toggle the

worklight on and off.

Ghost Voltages
The approximate input resistance of 15k

Ω

will reduce the possibility of

false readings due to ghost voltages on de-energized lines.

Lead Spacing

Molded lead holders on the back of the ET200 are spaced correctly

to test tamper-resistant outlets.

OPERaTING INSTRUCTIONS

SyMbOLS

+

Positive DC Voltage

Warning or Caution

Negative DC Voltage

Dangerous levels

~

aC Voltage

Double Insulated Class II

Earth Ground

ETL Certification

QuickTime™ and a

Photo - JPEG decompressor

are needed to see this picture.

This product has been tested to the requirements of

CaN/CSa-C22.2 No. 61010-1, second edition, including

amendment 1, or a later version of the same standard

incorporating the same level of testing requirements

CaT III

CaT IV

Designed for transient protection

on indoor measurements at

installations connected directly

to the primary source. Examples

include distribution panels and

lighting systems in large buildings.

Designed for transient protection

on outdoor measurements taken

at the primary supply voltage

source. Examples include outdoor

overhead or underground utility

service and electricity meter.

Measuring Voltages

Time spent operational at voltages above 277V must be less than

60 seconds, with a cool-off time of at least 5 minutes.

Tester will turn on automatically when voltage is applied.

aC Voltage Measurement

DC Voltage Measurement