Electrical installation

Important notes

6

l

32

BA 33.0005−EN 2.0

6

Electrical installation

6.1

Important notes

{

Danger!

Hazardous voltage on the power connections even when disconnected from
mains: residual voltage >60 V!
Before working on the power connections, always disconnect the drive
component from the mains and wait until the motor is at standstill.
Verify safe isolation from supply!

(

Stop!

Electrical connections must be carried out in accordance with the national and
regional regulations!

Observe tolerances according to IEC/EN 60034−1:

– Voltage ±5 %
– Frequency ±2 %
– Wave form, symmetry (increases heating and affects electromagnetic

compatibility)

Observe notes on wiring, information on the nameplate, and the connection scheme in the
terminal box.

ƒ

The connection must ensure a continuous and safe electrical supply, i.e.
– no loose wire ends,
– use assigned cable end fittings,
– ensure good electrical conductivity of the contact (remove residual lacquer) if an

(additional) PE connection on the motor housing is used),

– establish a safe PE conductor connection,
– tighten the plugin connector to the limit stop.
– After the connection is completed, make sure that all connections on the terminal

board are firmly tightened.

ƒ

The smallest air gaps between uncoated, live parts and against earth must not fall
below the following values.