Electrical installation

Three−phase AC motor operation on a frequency inverter

6

l

33

BA 33.0005−EN 2.0

Minimum requirements for basic
insulation according to IEC/EN
60664−1 (CE)

Higher requirements for UL design

Motor diameter

3.87 mm

6.4 mm

< 178 mm

9.5 mm

> 178 mm

ƒ

The terminal box has to be free of foreign bodies, dirt, and humidity.

ƒ

All unused cable entries and the box itself must be sealed against dust and water.

6.2

Three−phase AC motor operation on a frequency inverter

(

Stop!

Motors MF

LMA are only suitable for frequency inverter operation.

L−force three−phase AC motors M

LLMA are suitable for the operation on Lenze frequency

inverters and can be combined without restriction.

If another inverter is used for operation, the voltage peaks (U

pp

) for given rise times (t

R

) as

shown in the diagram must not be exceeded.

MT−MDXMA−005.iso/dms

Fig. 2

Permissible voltage peaks for frequency inverter operation (characteristic according to IEC
60034−25, curve A)