Troubleshooting and fault elimination

9

l

58

BA 33.0005−EN 2.0

Remedy

Cause

Fault
Incorrect direction of
rotation of the motor,
correct display on the
controller

Motor cable polarity is reversed

Check and correct polarity

Encoder cable polarity is reversed

Motor rotates normally
but does not generates the
expected torque

Motor cable interchanged cyclically

Connect the phases at the motor cable connection correctly

Motor rotates in one
direction at maximum
speed in an uncontrolled
manner

Motor cable interchanged cyclically

Check motor connection and, if necessary, correct it

Polarity of encoder cable reversed

Check encoder connection and, if necessary, correct it

Motor rotates slowly in
one direction and cannot
be influenced by the drive
controller

Polarity of motor cable and encoder
cable reversed

Check the polarity and correct it

Unsteady running

Shielding of motor cable or resolve
cable inadequate

Check shielding and earth connection

Gain of the drive controller too high

Adapt gain of the controller (see operating instructions for
drive controller)

Vibrations

Insufficiently balancing of coupling
elements or machine

Rebalance

Inadequate alignment of drive train

Realign machine, if necessary, check foundation

Loose fixing screws

Check screwed connections and tighten them if necessary

Running noises

Foreign particles inside the motor

Repair by manufacturer if necessary

Bearing damage

Surface
temperature > 140°C

Overload of the drive

l

Check overload and reduce through longer acceleration
times, if necessary

l

Check winding temperature

Heat dissipation impeded by dirt
deposits

Clean surface and cooling ribs of the drives