Safety instructions

Residual hazards

2

l

52

EDK94AMH24 DE/EN/FR/ES/IT 3.1

2.2

Residual hazards

Protection of persons

ƒ

Before starting work on the controller, check that the power terminals are
deenergised
– because the power terminals U, V, W, +UG and −UG carry hazardous voltages for at

least 3 minutes after mains disconnection.

– because the power terminals U, V, W, +UG and −UG carry hazardous voltages when

the motor is stopped.

Device protection

ƒ

Plug on or pull off all pluggable terminals only in deenergised condition!

ƒ

Detach the controllers only in deenergised conditions from their installation
backplanes or the back panel of the control cabinet!

ƒ

Cyclic switching on and off of the mains voltage can overload and destroy the input
current limitation of the controller:
– Cyclic mains switching of 5−times in 5 minutes is permissible without restrictions.

Motor protection

ƒ

Depending on the controller settings, the connected motor can be overheated by:
– For instance, longer DC−braking operations.
– Longer operation of self−ventilated motors at low speed.

Protection of the machine/system

ƒ

Drives can reach dangerous overspeeds (e.g. setting of high output frequencies in
connection with motors and machines unsuitable for such conditions):
– The controllers do not offer any protection against such operating conditions. Use

additional components for this purpose.