Wiring the device modules

Communication modules

8

l

73

EDK94AMH24 DE/EN/FR/ES/IT 3.1

DIP switch

Pos.

Description

A

Addressing of the station

For addressing purposes, every station must be given an unambiguous address.

Valid address range: 1

… 126

The address can be set freely via the front−panel switch.

)

Note!

ƒ

For S1 − S7 = OFF (Lenze setting):
When switching on the module, the configuration set under code C00899
becomes active.

ƒ

For one of the switches S1 − S7 = ON:
When switching on the module, the address resulting from the switch
setting becomes active.

Switch off the voltage supply of the communication module and then on again
in order to activate changed settings.

Address settings through the DIP switch (device front)

The sum of the values (identical with package labelling) results in the station address to be
set:

Example:

Switch

S7

S6

S5

S4

S3

S2

S1

Package labelling

«64»

«32»

«16»

«8»

«4»

«2»

«1»

Switch state

0

0

1

0

1

1

1

Address (= 23)

0

0

16

0

4

2

1

Displays

LED

Description

Pos.

Colour

Condition

MS

Green

On

The communication module is supplied with voltage and connected to
the standard device.

Blinking

The communication module is supplied with voltage, but has no
connection to the standard device. (The standard device is switched off,
initialising, or not present.)

ME

Red

On

An error in the communication module has occurred.

BS

Green

Blinking

Communication via the communication module has been established.
PROFIBUS communication is active.

BE

Red

On

Bus monitoring has been triggered.

DE

Red

On

The communication module is not accepted by the standard device. (See
notes in the documentation for the standard device.)