Technical data, Electrical data, Output data – Lenze E94AMHE User Manual

Page 58

Advertising
background image

Technical data

Electrical data

3

l

58

EDK94AMH24 DE/EN/FR/ES/IT 3.1

Output data

Voltage

Frequency

1)

Current [A]

Number of

phases

Type

[V]

[Hz]

max. +45 °C



max. +55 °C



E94AMxE0024

0 − 230/400/500

0 − 599

1.5/1.5/1.3

1.1/1.1/1.0

3

E94AMxE0034

0 − 230/400/500

0 − 599

2.5/2.5/2.2

1.9/1.9/1.7

3

E94AMxE0044

0 − 230/400/500

0 − 599

4/4/3.5

3/3/2.6

3

E94AMxE0074

0 − 230/400/500

0 − 599

7/7/6.1

5.3/5.3/4.6

3

E94AMxE0094

0 − 230/400/500

0 − 599

9.3/9.3/8.2

7.0/7.0/6.2

3

E94AMxE0134

0 − 230/400/500

0 − 599

13/13/11.4

9.8/9.8/8.6

3

E94AMxE0174

0 − 230/400/500

0 − 599

16.5/16.5/14.4

12.4/12.4/10.8

3

E94AMxE0244

0 − 230/400/500

0 − 599

23.5/23.5/20.6

17.6/17.6/15.5

3

E94AMxE0324

0 − 230/400/500

0 − 599

32.0/32.0/25.9

24.0/24.0/19.4

3

 Temperature in the control cabinet

Power loss P

V

[W]

Type

when operating with rated output current I

aN

when controller is inhibited

E94AMxE0024

65

80

95

40

E94AMxE0034

75

95

110

E94AMxE0044

90

120

130

E94AMxE0074

105

145

170

E94AMxE0094

130

170

205

E94AMxE0134

160

215

255

E94AMxE0174

185

255

300

E94AMxE0244

235

320

385

E94AMxE0324

290

405

490

Assignment of installation backplane ˘ standard device

Axis controller
type

Installation backplane type

Fuse

Device size

E94AMxE0024

E94AZPM0044

Siba 5020106.16A

1

E94AMxE0034
E94AMxE0044
E94AMxE0074

E94AZPM0094

Siba 5020106.40A

2

E94AMxE0094
E94AMxE0134

E94AZPM0244

Siba 2029221.100A

(tightening torque: 3.4 Nm

(30 lb−in))

3

E94AMxE0174
E94AMxE0244

E94AMxE0324

E94AZPM0324

Siba 2029221.100A

(tightening torque: 3.4 Nm

(30 lb−in))

3

Advertising