2 technical data, 2technical data – Lenze E94AYAE SM301 User Manual

Page 28

Advertising
background image

2

Technical data

EDK94AYAE DE/EN/FR/ES/IT 3.0

28

l

H1_Daten−LESE SM301 HB SiFu

2

Technical data

24 V supply

The module and the safe output must be supplied with 24 V from safely separated power
supply units. To maintain electrical isolations, separate voltage supplies are required.

Detailed features of the 24−V supply

Terminal

Specification

[Unit]

min.

typ.

max.

+, −

Supply voltage of the module via a safely
separated power supply unit (SELV/PELV)

[V]

19.2

24

30

Input current

[mA]

350

24O, GO

Supply voltage of the safe output via a safely
separated power supply unit (SELV/PELV)

[V]

18

24

30

Input current

[mA]

1100

Safety functions

,

The manual for the safety module contains information on the safety
functions.

Advertising