Electrical installation

3

EDK94AYAE DE/EN/FR/ES/IT 3.0

29

l

H1_E_INST−−−−(DUMMYSEITEVOR)−−−

3

Electrical installation

)

Note!

For installation, the documentation of the controller must be observed.

Addressing

The safety address serves to clearly assign the safety modules of the SM301 type in systems
with several drives. The address "0" is not permissible.

Address switch

The safety address can be set in the left part of the housing by means of the DIP switch

0.

For setting the switch, use an appropriately small tool, e. g. a probe. The switch can only be
set if the module is not connected to a standard device. Via the switch, addresses in the
range of 0 ... 1023 can be set. Alterations by the switch with regard to the address are only
activated when the 24−V supply is switched on. The address setting "0" requires the setting
by the address code.

DIP switch

0

Labelling

1

2

3

4

5

6

7

8

9

0

Value of the address bit

1

2

4

8

16

32

64

128

256

512

)

Note!

In the SM301 safety module as of version VA 1.xx, the address 0 is replaced as
follows:

ƒ

With the address saved in the safety module in the parameter
"Safety address" (C15111).

ƒ

If the address 0 canot be replaced, the module reports an error.

)

Note!

A safety bus system (PROFIsafe) can only be operated via the upper module
slot (MXI1) of the Servo Drive 9400.