Safety engineering – Lenze E94AYAB − SM100 User Manual

Page 16

Advertising
background image

Safety engineering

Device modules
Safety module SM100

1

l

16

EDS94AYAB EN 2.1

Signals

X80

Marking

Description

Electrical data

SIA

Input first shutdown path

SIA: I

typ

= 160 mA

GI

GND potential for SIA/SIB

LOW: −3 ... 5 V,
HIGH: 15 ... 30 V,

SIB

Input second shutdown path

SIB: I

typ

= 28 mA

Supply through safely
separated power supply unit
(SELV/PELV)

GO

GND potential feedback

24 V, max. 0.7 A,
short−circuit−proof,
LOW−active,
Supply through safely
separated power supply unit
(SELV/PELV)

24O

24 V supply feedback

SSP9400X80

DO1

Non−safe signalling output: "Safe pulse
inhibit"

Terminal data

Conductor cross−section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb−in]

Rigid

0.2 ... 2.5

24 ... 12

Spring terminal

Wire end ferrule,
insulated

0.2 ... 1.5

24 ... 16

Twin wire end
ferrule

0.5 ... 1.0

20 ... 18

Stripping length / contact length: 10 mm

Information for the exchange of modules of different hardware versions

up to HW: VB

from HW: VC

Comment

SI1

SIA

The exchange of the spring terminal
is required!

GI

GI

SI2

SIB

GO

GO

24O

24O

DO1

DO1

Advertising