Acceptance
Description

1

l

19

EDS94AYAB EN 2.1

1.3

Acceptance

1.3.1

Description

The machine manufacturer must check and prove the operability of the safety functions
used.

Inspector

The machine manufacturer must authorise a person with expertise and knowledge of the
safety functions to carry out the test.

Protocol

The test result of every safety function must be documented and signed.

)

Note!

If parameters of the safety function are changed, the test must be repeated
and recorded in the test report.

Scope

A complete test comprises the following:

ƒ

Documentation of the plant including the safety functions.
– Plant description and overview map
– Description of the safety devices
– Safety functions used

ƒ

Functional test of the safety functions used

ƒ

Preparing the test report
– Documenting the functional test
– Controlling the parameters
– Signing

ƒ

Preparing the appendix with test records
– Protocols from the plant
– External recording

1.3.2

Periodic inspections

The correct sequence of the safety−oriented functions must be checked in periodic
inspections. The risk analysis or applicable regulations determine the time distances
between the tests. The inspection interval should not exceed one year.