Assignment of the terminals, Electrical installation – Lenze E82ZAFPC010 User Manual

Page 61

Advertising
background image

Electrical installation

Assignment of the terminals

6

EDK82ZAFPC-010 DE/EN/FR 6.0

61

H2_BelegungAnschlKlemmen-klemmbesch-010

Assignment of the terminals

Terminal

X3.1/

Designation

Function / level

PES

Additional HF shield termination

A

T/R(A)

RS485 data line A

B

T/R(B)

RS485 data line B

Terminal
X3.2/

Designation

Function / level

59

External DC voltage supply for the function module

+24 V DC

±

10% (reference: GND1)

Current consumption on 24 V DC: 80 mA

The current for looping through the supply voltage to other nodes
via terminal 59 must be max. 3 A.

7

GND1

Reference potential for X3.3/20

Terminal
X3.3/

Designation

Function / level

7

GND1

Reference potential for X3.3/20

39

GND2

Reference potential for controller inhibit (CINH) at X3.3/28

28

CINH

Controller inhibit

Input resistance: 3.3 k

Start = HIGH (+12 ... +30 V)
Stop = LOW (0 ... +3 V)
(reference: GND2)

20

DC voltage source for external supply of controller inhibit (CINH)

+20 V (reference: GND1)
I

max

= 10 mA