Bus cable length, 6electrical installation – Lenze E82ZAFCC100 User Manual

Page 54

Advertising
background image

6

Electrical installation

Bus cable length

EDK82ZAFCC-100 DE/EN/FR 5.0

54

H2 BusLeitgsLaenge-Leitungslaenge_3

Bus cable length

It is absolutely necessary to comply with the permissible cable lengths.
1. Please check the compliance with the total cable length in Tab. 1.
The total cable length is defined by the baud rate.

Baud rate [kbps]

Max. bus length [m]

20

3900

50

1500

125

610

250

270

500

100

1000

9

Tab. 1

Total cable length

2. Please check the compliance with the segment cable length in Tab. 2.
The segment cable length is defined by the cable cross-section and the number of bus
devices. Without repeater the segment cable length corresponds to the total cable length.

Bus device

Cable cross-section

0.25 mm

2

0.5 mm

2

0.75 mm

2

1.0 mm

2

2

240 m

430 m

650 m

940 m

5

230 m

420 m

640 m

920 m

10

230 m

410 m

620 m

900 m

20

210 m

390 m

580 m

850 m

32

200 m

360 m

550 m

800 m

63

170 m

310 m

470 m

690 m

Tab. 2

Segment cable length

Advertising