6electrical installation – Lenze E82ZAFCC100 User Manual

Page 56

Advertising
background image

6

Electrical installation

Bus cable length

EDK82ZAFCC-100 DE/EN/FR 5.0

56

H2 BusLeitgsLaenge-Leitungslaenge_3

Check repeater application

Given:

Baud rate:

125 kbps

Cable cross-section:

0.5 mm

2

Number of nodes:

28

Cable length:

450 m

Procedure

Cable length

See

1. Total cable length at 125 kbps:

610 m

from Tab. 1

2. Segment cable length for 28 bus nodes and a cable

cross-section of 0.5 mm

2

:

360 m

from Tab. 2

3. Comparison: The value under 2. is smaller than the cable length of 450 m.

Conclusion

It is not possible to use a cable length of 450 m without using a repeater.

After 360 m (item 2.), a repeater must be installed.

Result

The Lenze repeater type 2176 is used (cable reduction: 30 m)

Calculation of the maximum cable length:
First segment: 360 m
Second segment: 360 m (according to Tab. 1) minus 30 m (cable reduction when a repeater is
used)
Maximum possible cable length with repeater: 690 m.
Now it is possible to use the required cable length.

Note!

The use of a further repeater is recommended as

ƒ

Service interface
Advantage: Trouble-free connection during running bus operation is
possible.

ƒ

Calibration interface
Advantage: Calibration/programming device remains isolated.