7 commissioning, Possible settings via dip switch, Commissioning – Lenze E82ZAFCC100 User Manual
Page 57
![background image](/manuals/565935/57/background.png)
Commissioning
Possible settings via DIP switch
7
EDK82ZAFCC-100 DE/EN/FR 5.0
57
H1inbet-Baudrate
7
Commissioning
Possible settings via DIP switch
ON
OFF
1
6
ON
2
7
3
8
4
9
5
10
The DIP switches on the front serve to set the
ƒ node address (switches 1 ... 6)
ƒ baud rate (switches 7 ... 9)
Switch 10 does not have any function.
The Lenze setting of all DIP switches is OFF.
Note!
Settings via codes
ƒ
In the Lenze setting (all switches OFF), all values from codes C0350 (node
address) and C0351 (baud rate) are accepted.
ƒ
Changes to codes are accepted by:
– A voltage supply switch-off and switch-on or
– A ”Reset node” with C0358 = 1
ƒ
C0350 is inactive if at least one of the switches 1 ... 6 has been set to the
ON position before the mains is reconnected.
ƒ
C0351 is inactive if at least one of the switches 7 ... 9 has been set to the
ON position before the mains is reconnected.
ƒ
Detailed information on the codes is provided in the CAN communication
manual and the documentation of the standard device.