Commissioning

Possible settings via DIP switch

7

EDK82ZAFCC-100 DE/EN/FR 5.0

57

H1inbet-Baudrate

7

Commissioning

Possible settings via DIP switch

ON

OFF

1

6

ON

2

7

3

8

4

9

5

10

The DIP switches on the front serve to set the
ƒ node address (switches 1 ... 6)
ƒ baud rate (switches 7 ... 9)
Switch 10 does not have any function.
The Lenze setting of all DIP switches is OFF.

Note!

Settings via codes

ƒ

In the Lenze setting (all switches OFF), all values from codes C0350 (node
address) and C0351 (baud rate) are accepted.

ƒ

Changes to codes are accepted by:
– A voltage supply switch-off and switch-on or
– A ”Reset node” with C0358 = 1

ƒ

C0350 is inactive if at least one of the switches 1 ... 6 has been set to the
ON position before the mains is reconnected.

ƒ

C0351 is inactive if at least one of the switches 7 ... 9 has been set to the
ON position before the mains is reconnected.

ƒ

Detailed information on the codes is provided in the CAN communication
manual and the documentation of the standard device.