Electrical installation – Lenze E82ZAFCC100 User Manual

Page 55

Advertising
background image

Electrical installation

Bus cable length

6

EDK82ZAFCC-100 DE/EN/FR 5.0

55

H2 BusLeitgsLaenge-Leitungslaenge_3

3. Please compare the detected values.
If the value in Tab. 2 is smaller than the total cable length in Tab. 1, repeaters must be used.
Repeaters divide the total cable length into segments.

Note!

ƒ

Please note the reduction of the total cable length due to the signal delay
of the repeater (see example (56).

ƒ

Mixed operation
– With mixed operation, different devices are connected to the same

mains.

– If the total cable lengths of the devices are different at the same baud

rate, the smaller value must be used to determine the max. cable
length.

Example: Selection help

Given:

Cable cross-section:

0.5 mm

2

(according to cable specification 49)

Number of devices
connected:

63

Repeater:

Lenze repeater, type 2176 (cable reduction: 30 m)

With maximum number of bus devices (63) the following cable lengths/number of
repeaters must be complied with:

Baud rate [kbits/s]

20

50

125

250

500

1000

Max. cable length [m]

3900

1500

610

270

100

9

Segment cable length [m]

310

310

310

270

100

9

Number of repeaters

13

5

1

-

-

-