Technical data, 2 connections and i/o, 1 p1 - input power (mains) connection – Lenze E94P v4.0 User Manual

Page 8

Advertising
background image

6

13433283_P94MI01D_EN

Technical Data

2.2

Connections and I/O

2.2.1

P1 - Input Power (Mains) Connection

Standard Models

1

2

3

4

L3

L2

L1

PE

Doubler Models

1

2

3

4

L2/N

L1

N

PE

Pin Name Function

Name Function

1

PE

Protective Earth (Ground)

PE

Protective Earth (Ground)

2

L1

AC Power in

N

AC Power Neutral (120V Doubler only)

3

L2

AC Power in

L1

AC Power in

4

L3

AC Power in (3~ models only)

L2/N AC Power in (non-doubler operation)

Fuse

PE

L1, L2, L3

EN 60204

UL

Type

[A]

1~/3~

[A]

1~/3~

[A]

1~/3~

[mm

2

]

[AWG]

[mm]

[in]

[Nm]

[lb-in]

[mm

2

]

[AWG]

1~/3~

[mm]

[in]

[Nm]

[lb-in]

E94_020S1N_~

M20/M10

C20/C10

20/10

2.5

14

6

0.25

0.5
4.5

2.5/2.5

14/14

6

0.25

0.5
4.5

E94_040S1N_~

M32/M20

C32/C20

30/20

4

12

4/2.5

12/14

E94_020S2F_~

M20

C20

20

2.5

14

6

0.25

0.5
4.5

2.5

14

6

0.25

0.5
4.5

E94_040S2F_~

M20

C20

20

E94_080S2F_~

M32

C32

32

4

12

4

12

E94_100S2F_~

M40

C40

40

6

10

6

10

E94_020Y2N_~

M20/M16

C20/C16

20/15

2.5

14

6

0.25

0.5
4.5

2.5/2.5

14/14

6

0.25

0.5
4.5

E94_040Y2N_~

M20/M16

C20/C16

20/15

E94_080Y2N_~

M32/M20

C32/C20

30/20

4

12

4/2.5

12/14

E94_100Y2N_~

M32/M20

C32/C20

30/20

6

10

6/2.5

10/14

0.79

7

E94_120Y2N_~

M50/M32

C50/C32

50/30

6

10

6/4

10/12

0.5
4.5

E94_180T2N_~

M40

C40

40

6

10

0.79

7

6

10

0.79

7

E94_020T4N_~

M10

C10

10

2.5

14

6

0.25

0.5
4.5

2.5

14

6

0.25

0.5
4.5

E94_040T4N_~

M10

C10

10

E94_060T4N_~

M20

C20

20

E94_090T4N_~

M25

C25

25

1)

Installations with high fault current due to large supply mains may require a type D circuit breaker.

2)

UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN, JJS or equivalent.

3)

Thermal-magnetic type breakers preferred.

WARNING!

The PositionServo drive runs on phase-to-phase voltage. For the standard drive, either a delta or wye transformer may be used for
3-phase input. However, for reinforced insulation of user accessible I/O circuits, each phase voltage to ground must be less than or
equal to 300VAC rms. This means that the power system must use center grounded wye secondary configuration for 400/480VAC
mains.

STOP!

For the E94 _020S1N_~ and E94_040S1N_~ doubler models, do NOT apply 240VAC to the N and L1 terminals. Severe damage to
the drive will result.

1)

2)
3)