Safety instructions

Safety instructions for the installation according to UL

1

l

65

EDKCSCE040 DE/EN/FR 3.0

1.3

Safety instructions for the installation according to UL

J

Warnings!

General markings:

ƒ

Use 60/75 °C or 75 °C copper wire only.

ƒ

Maximum ambient temperature 55 °C, with reduced output
current.

Markings provided for the supply units:

ƒ

Suitable for use on a circuit capable of delivering not more than
5000 rms symmetrical amperes, 480 V max, when protected by
K5 or H Fuses (400/480 V devices).

ƒ

Alternate − Circuit breakers (either inverse−time, instantaneous
trip types or combination motor controller type E) may be used in
lieu of above fuses when it is shown that the let−through
energy (i

2

t) and peak let−through current (I

p

) of the inverse−time

current−limiting circuit breaker will be less than that of the
non−semiconductor type K5 fuses with which the drive has been
tested.

ƒ

Alternate − An inverse−time circuit breaker may be used, sized
upon the input rating of the drive, multiplied by 300 %.

Markings provided for the inverter units:

ƒ

The inverter units shall be used with supply units which are
provided with overvoltage devices or systems in accordance with
UL840 2nd ed., Table 5.1.

ƒ

The devices are provided with integral overload and integral
thermal protection for the motor.

ƒ

The devices are not provided with overspeed protection.

Terminal tightening torque of lb−in (Nm)

Terminal

lb−in

Nm

X 21, X 22, X 23, X 24

10.6 ... 13.3

1.2 ... 1.5

X4, X6, X14

1.95 ... 2.2

0.22 ... 0.25

X 25

4.4 ... 7.1

0.5 ... 0.8

Wiring diagram AWG

Terminal

AWG

X 21, X 22, X 23, X 24

12 ... 8

X4, X6, X14

28 ... 16

X 25

24 ... 12